Application Set-up Examples
6 Application Set-up Examples
The examples in this section are intended as a quick reference for common applications.
•
Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional
Settings).
•
Parameters associated with the terminals and their settings are shown next to the drawings.
•
Required switch settings for analog terminals A53 or A54 are also shown.
NOTICE
When using the optional STO feature, a jumper wire may be required between terminal 12 (or 13) and terminal 37 for
the frequency converter to operate with factory default programming values.
6
6
6.1 Application Examples
6.1.1 Feedback
FC
12
+24 V
13
+24 V
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
32
D IN
D IN
33
37
D IN
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A 54
Table 6.1 Analog Current Feedback Transducer
32
®
VLT
AQUA Drive FC 202
Parameters
Function
Parameter 6-22 Terminal
54 Low Current
Parameter 6-23 Terminal
54 High Current
Parameter 6-24 Terminal
54 Low Ref./Feedb.
Value
Parameter 6-25 Terminal
54 High Ref./Feedb.
Value
* = Default value
Notes/comments:
+
D IN 37 is an option.
-
4-20 mA
Danfoss A/S © 10/2016 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
Setting
D IN
19
4 mA*
COM
20
D IN
27
20
D IN
29
D IN
32
mA*
D IN
33
0*
D IN
37
+10 V
50
50*
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A54
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
Parameters
Function
Parameter 6-20 Ter
0.07 V*
minal 54 Low
Voltage
Parameter 6-21 Ter
10 V*
minal 54 High
Voltage
Parameter 6-24 Ter
0*
minal 54 Low Ref./
Feedb. Value
Parameter 6-25 Ter
50*
minal 54 High Ref./
Feedb. Value
+
* = Default value
Notes/comments:
-
D IN 37 is an option.
0 - 10V