Specifications

8.4 Ambient Conditions

Environment
Enclosure
Vibration test
Max. THVD
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide..
1)
Derating for high ambient temperature, see special conditions in the Design Guide
8
8

8.5 Cable Specifications

Cable lengths and cross-sections for control cables1)
Max. motor cable length, shielded
Max. motor cable length, non-shielded
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1)
For power cables, see electrical tables in chapter 8.1 Electrical Data.
64
Instruction Manual
S test
2
1)
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
IP20/Chassis, IP21/Type 1, IP55/ Type 12, IP66/ Type 4X
5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Max. 122 °F [50 °C] (24-hour average maximum 113 °F [45 °C])
class Kd
32 °F [0 °C]
14 °F [-10 °C]
-13 to +49/158 °F [-25 to +65/70 °C]
3300 ft [1000 m]
EN 61800-3
EN 61800-3
500 ft [150 m]
1000 ft [300 m]
2
1.5 mm
/16 AWG
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
0.25 mm
2
/24 AWG
MG33AN22
1.0 g
10%