Kessel Ecolift XL Instructions For Installation, Operation And Maintenance page 83

Backwater lifting station
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 45
Display text
Thermal protection 1A
Thermal protection 1B
Thermal protection 2A
Thermal protection 2B
Maintenance date due
*Caution: Check position of the operating valve!
The control attempts to close the flap 3 x in the interval and perhaps eliminate the blocking object in the process.
If the object can be removed by the flap movement during these cycles, the system is ready to be used again.
If this does not work, the system switches to fault. Acknowledgement of the signal is possible.It is also possible
to remove the object by flushing the line. This can be checked by pressing the test key again. In the event of a
negative result, the fault message will appear again; the object must be eliminated as described under remedial
measure.
03/2015
Troubleshooting
Possible cause
A thermal fuse on one of the
pumps has triggered.
The maintenance date has
been reached
No maintenance date entered
83 / 264
Remedial measure
Inform Customer Services
before putting back into
operation, pump must be
checked/replaced.
Carry out maintenance
Enter maintenance date (see
control unit instructions)