Maintenance Card - Kessel Ecolift XL Instructions For Installation, Operation And Maintenance

Backwater lifting station
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 45
Inspection/maintenance Ecolift XL
Please note the safety instructions
Building description
Building
Street
Postcode, city
Contact
System variant
Serial number
Pump type
Inspection: Once a month by the operator:
No.
Test
1
Check the display of control unit 1 Comfort Plus for possible fault messages
2
Manual function test on Comfort Plus and on control unit for redundant valve if present,
close flap A (sewer side) (using flap test hand symbol)
Make sure of inflow (clear water) ➞ wait to see if the pump starts working
3
Manual function test on control unit for redundant valve if present
close flap B (house side) (using flap test hand symbol)
Make sure of inflow (clear water) ➞ wait to see if the pump starts working
A rising level can be seen on the display. Inlet until switch-on point 1 or switch-on point 2 has been reached, then
pump operation starts.
"On" level: ______________________
"Off" level: ______________________
Since pumps 1 and 2 pump alternately, always wait two operating cycles.
4
Test compressor set ➞ listen to check whether the compressor is running. Use manual
pump to free hose of condensation
5
If pump is pumping ➞ stop inflow
6
Open the flap of the control unit redundant flap again manually, then
7
Open the flap of the Comfort Plus control unit again
If a fault message appears, proceed according to the control unit instructions.
Maintenance: by a maintenance expert in accordance with the maintenance interval:
8
Steps 1-7 must be carried out as described above.
9
Open the inspection chamber and check the cover seal for damage
10
Carry out a visual inspection of the upper section and visual inspection of the inspection
chamber and the control cable
11
Disconnect the system from the mains and secure it against being switched on again
03/2015
Maintenance
Mono ❏ Duo ❏
1 ❏ 2 ❏
77 / 264
Done record
yes no

Advertisement

Table of Contents
loading

This manual is also suitable for:

010-694

Table of Contents