Specifications
Speed accuracy (open-loop)
Speed accuracy (closed-loop), depending on resolution of feedback device
Torque control accuracy (speed feedback)
All control characteristics are based on a 4-pole asynchronous motor
Environment:
Enclosure
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
3)
Ambient temperature
≤ 5 hp [3.7 kW] (200–240V), ≤ 10 hp [7.5 kW] (400–480/ 500V)
1)
Only for
≤ 5 hp [3.7 kW] (200–240V), ≤ 10 hp [7.5 kW] (400–480/ 500V)
2)
As enclosure kit for
3)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide.
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches a predefined level. An overload temperature cannot be reset until the temperature of the heatsink is
below the values stated in the tables on the following pages (guideline - these temperatures may vary for different
power sizes, frame sizes, enclosure ratings, etc.).
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive constantly checks for critical levels of internal temperature, load current, high
voltage on the intermediate circuit and low motor speeds. As a response to a critical level, the adjustable
frequency drive can adjust the switching frequency and/or change the switching pattern in order to ensure the
performance of the adjustable frequency drive.
VLT
®
AutomationDrive Instruction
Manual
5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
Max. 122°F [50°C] (24-hour average maximum 113°F [45°C])
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
®
MG.33.AI.22 - VLT
is a registered Danfoss trademark
30–4000 rpm: error ±8rpm
0–6000 rpm: error ±0.15 rpm
max error±5% of rated torque
1)
2)
IP20
/ Type 1, IP21
/ Type 1, IP55/ Type 12, IP 66
-13°–149°/158°F [-25°–+65°/70°C]
EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
1.0g
class Kd
32°F [0°C]
14°F [-10°C]
3280 ft [1000 m]
10
10
10-15