Specifications
Enclosure
Size
A1
A2
A3
B3
B4
C3
C4
A4
A5
B1
B2
C1
C2
10
10
D
E
F
Table 10.2 380–500V, Frame Sizes A, B, C, D, E, and F
10-18
FC 300 Power
Recommended
fuse size
[kW]
0.37–1.5
gG-10
0.37–4.0
gG-10 (0.37–3)
gG-16 (4)
5.5–7.5
gG-16
11–15
gG-40
18.5–30
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
37–45
gG-100 (37)
gG-160 (45)
55–75
aR-200 (55)
aR-250 (75)
0.37–4
gG-10 (0.37–3)
gG-16 (4)
0.37–7.5
gG-10 (0.37–3)
gG-16 (4–7.5)
11–15
gG-40
18.5–22
gG-50 (18.5)
gG-63 (22)
30–45
gG-80 (30)
gG-100 (37)
gG-160 (45)
55–75
aR-200 (55)
aR-250 (75)
gG-300 (90)
gG-350 (110)
90–200
gG-400 (132)
gG-500 (160)
gG-630 (200)
aR-700 (250)
250–400
aR-900 (315–400)
aR-1600 (450–500)
450–800
aR-2000 (560–630)
aR-2500 (710–800)
MG.33.AI.22 - VLT
VLT
®
AutomationDrive Instruction
Manual
Recommended
Max. fuse
gG-25
gG-25
gG-32
gG-63
gG-125
gG-150 (37)
gG-160 (45)
aR-250
gG-32
gG-32
gG-80
gG-100
gG-160
aR-250
gG-300 (90)
gG-350 (110)
gG-400 (132)
gG-500 (160)
gG-630 (200)
aR-700 (250)
aR-900 (315–400)
aR-1600 (450–500)
aR-2000 (7560–630)
aR-2500 (710–800)
®
is a registered Danfoss trademark
Recommended circuit
Max. trip level
breaker
Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
-
-
-
[A]
16
25
25
50
100
150
250
25
25
63
100
160
250
-
-
-