Danfoss VLT AutomationDrive FC 303 Instruction Manual page 97

Table of Contents

Advertisement

Specifications
FC 300
[kW]
0.25–0.37
0.55–1.1
1.5
2.2
3.0
3.7
5.5
7.5
11
15–18.5
22
30
37
Table 10.7 200–240V, Frame Sizes A, B, and C
1) KTS fuses from Bussmann may substitute KTN for 240V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V adjustable frequency drives.
10
10
FC 300
[kW]
0.37–1.1
1.5–2.2
3
4
5.5
7.5
11
15
18
22
30
37
45
55
75
Table 10.8 380–500V, Frame Sizes A, B, and C
10-22
VLT
Manual
Recommended max. fuse
Bussmann
2)
Type JFHR2
FWX-5
FWX-10
FWX-15
FWX-20
FWX-25
FWX-30
FWX-50
FWX-60
FWX-80
FWX-125
FWX-150
FWX-200
FWX-250
Bussmann
Bussmann
Type RK1
Type J
KTS-R-6
JKS-6
KTS-R-10
JKS-10
KTS-R-15
JKS-15
KTS-R-20
JKS-20
KTS-R-25
JKS-25
KTS-R-30
JKS-30
KTS-R-40
JKS-40
KTS-R-50
JKS-50
KTS-R-60
JKS-60
KTS-R-80
JKS-80
KTS-R-100
JKS-100
KTS-R-125
JKS-125
KTS-R-150
JKS-150
KTS-R-200
JKS-200
KTS-R-250
JKS-250
MG.33.AI.22 - VLT
®
AutomationDrive Instruction
Littel fuse
JFHR2
-
-
-
-
-
-
-
-
-
-
L25S-150
L25S-200
L25S-250
Recommended max. fuse
Bussmann
Bussmann
Type T
Type CC
JJS-6
FNQ-R-6
JJS-10
FNQ-R-10
JJS-15
FNQ-R-15
JJS-20
FNQ-R-20
JJS-25
FNQ-R-25
JJS-30
FNQ-R-30
JJS-40
JJS-50
JJS-60
JJS-80
JJS-100
JJS-125
JJS-150
JJS-200
JJS-250
®
is a registered Danfoss trademark
Ferraz-
Shawmut
4)
JFHR2
-
-
-
-
-
-
-
-
-
-
A25X-150
A25X-200
A25X-250
Bussmann
Type CC
KTK-R-6
KTK-R-10
KTK-R-15
KTK-R-20
KTK-R-25
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
J
HSJ-6
HSJ-10
HSJ-15
HSJ-20
HSJ-25
HSJ-30
HSJ-50
HSJ-60
HSJ-80
HSJ-125
HSJ-150
HSJ-200
HSJ-250
Bussmann
Type CC
LP-CC-6
LP-CC-10
LP-CC-15
LP-CC-20
LP-CC-25
LP-CC-30
-
-
-
-
-
-
-
-
-