Autobaud Serial 1" Sequence; Autonode Port 1" Sequence - gefran GFX4-IR Series Installation And Operation Manual

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

4.2
"autobauD serial 1"
Function
Adapt the serial communication speed and parity of the GFX4-
IR modules to the connected supervision terminal or PLC.
Green LED L1 "STATUS" mentioned in the procedure
can vary its behavior based on parameter Ld.1, which
is set to a default value of 16.
Procedure
1) Connect the serial cables for all modules on the network to
serial 1 and to the supervision terminal.
2) Set the rotary switch on the GFX4-IR modules to be
installed, or on all modules present in case of first installation,
to position "0+0".
3) Check that the green "STATUS" LEDs flash at high
frequency (10Hz).
4) The supervision terminal must transmit a series of generic
"MODBUS" read messages to the network.
5) The procedure is over when all of the green L1 "STATUS"
LEDs on the Geflex modules flash at a normal frequency
(2Hz) (if parameter 197 Ld.1 = 16 as default).
The new speed parameter is saved permanently in each
GFX4-IR; therefore, the "AUTOBAUD SERIAL 1" sequence
does not have to be run at subsequent power-ups.
When the rotary switch is turned, the green
"STATUS" LED stays on steadily for about 6 seconds,
after which it resumes normal operation and saves
the address.
4.1
""autonoDe port 1"
Function
Assigning the Function
Adapt the serial communication speed and parity of the GFX4-
IR modules to the connected supervision terminal or PLC.
Green LED L1 "STATUS" mentioned in the procedure
can vary its behavior based on parameter Ld.1, which
is set to a default value of 16.
Procedure
1) Connect the serial cables for all modules on the network to
serial 1 and to the supervision terminal.
2) Set the rotary switch on the GFX4-IR modules to be
installed, or on all modules present in case of first installation,
to position "0+0".
3) Check that the green "STATUS" LEDs flash at high
frequency (10Hz).
4) The supervision terminal must transmit a series of generic
"MODBUS" read messages to the network.
80404L_MHW_GFX4-IR_03-2020_ENG
sequence
sequence
INSTALLATION OF
SERIAL NETWORK 1
ModBus
?
The serial network communication
YES
speed is the same as for
GFX4-IR.
NO
"AUTOBAUD"
SERIAL 1
SEQUENCE
SETTING
THE NODE
ADDRESS
?
NO
YES
"AUTONODE"
SEQUENCE
OPERATIVE
FUNCTION
Green "STATUS" LED
flashes at 10 Hz
GEFLEX S1/S1 are connected
or the "FIELDBUS" PORT 2 is
present.
Green "STATUS" LED
flashes at 5Hz
45