Figure 44
Connection example for 4 single-phase loads, 3-phase line with neutral
Dip-Switches configuration
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
(HB Diagnostics active with P>30%)
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
Figure 45
Connection example for 4 single-phase transformer loads, 3-phase line with neutral
Dip-Switches configurations
Dip 1
Dip 2
Dip 3
Dip 4
OFF
OFF
OFF
- FIRING MODE: ZC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
See notes for use with inductive loads and transformers
80404L_MHW_GFX4-IR_03-2020_ENG
Dip 4
Dip 5
OFF
OFF
Dip 5
OFF
ON
P
Id = ___
V cosj
V = phase voltage (line - neutral)
P = power of each single-phase load
Id = load current
if resistive load cosj = 1
P
Id = _________
Is = _________
h . V . cosj
P = power of each single-phase load
V = phase voltage (line L1- line L2/N)
Vload = voltage on secondary (load)
Id = current in primary
Is = current in secondary (load)
h = transformer output (type 0.9)
if resistive load cosj = 1
P
Vload . cosj
33