gefran GFX4-IR Series Installation And Operation Manual page 34

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

Figure 46
Connection example for 3 independent single-phase loads in open delta, 3-phase line without neutral
Dip-Switches configuration
Dip 1
Dip 2
Dip 3
OFF
ON
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
Figure 47
Connection example for 1 3-phase star load without neutral (3 wires)
Dip-Switches configuration
Dip 1
Dip 2
Dip 3
ON
OFF
-
- FIRING MODE: ZC, BF, PA (P>6%)
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F" See table Fuse/Fuseholders
34
Dip 4
Dip 5
ON
OFF
Dip 4
Dip 5
ON
OFF
P
Id = ___
V cosj
V =
line voltage
P = power of each single-phase load
Id = load current
if resistive load cosj = 1
V
___
Id = ________
Vd =
V 3
V 3 V cosj
V =
line voltage
Vd =
load voltage
Id =
load current
P =
total power
if resistive load cosj = 1
80404L_MHW_GFX4-IR_03-2020_ENG