gefran GFX4-IR Series Installation And Operation Manual page 32

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

Figure 42
Connection example for 4 single-phase transformer loads, single-phase line L1-L2/N
Dip-Switches configurations
Dip 1
Dip 2
Dip 3
Dip 4
OFF
OFF
OFF
- FIRING MODE: ZC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
See notes for use with inductive loads and transformers
Figure 43
Connection example for 4 single-phase transformer loads, 3-phase line without neutral
Dip-Switches configurations
Dip 1
Dip 2
Dip 3
Dip 4
OFF
OFF
OFF
- FIRING MODE: ZC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE:
Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
See notes for use with inductive loads and transformers
32
Dip 5
OFF
ON
Dip 5
OFF
ON
P
Id = _________
Is = _________
h . V . cosj
P = power of each single-phase load
V = phase voltage (line L1- line L2/N)
Vload = voltage on secondary (load)
Id = current in primary
Is = current in secondary (load)
h = transformer output (type 0.9)
if resistive load cosj = 1
P
Id = _________
Is = _________
h . V . cosj
P = power of each single-phase load
V = phase voltage (line L1- line L2/N)
Vload = voltage on secondary (load)
Id = current in primary
Is = current in secondary (load)
h = transformer output (type 0.9)
if resistive load cosj = 1
80404L_MHW_GFX4-IR_03-2020_ENG
P
Vload . cosj
P
Vload . cosj

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfx4-ir 30Gfx4-ir 60Gfx4-ir 80Gfx4-ir 30-d-2-f

Table of Contents