Figure 52
Control of 1 triphase load open delta, and 1 single load on CH4 GFX4-IR...T40
Dip-Switches configuration
Dip 1
Dip 2
Dip 3
ON
ON
OFF
- FIRING MODE: ZC, BF, PA, HSC
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
Figure 53
Wiring example of three GFX4-IR...T40 with optimized line current sharing
NOTES:
1
The GFX4-IR T40 product is especially designed for open delta applications, but can control also other load configurations.
2
The GFX4-IR T40 can control a three-phase load closed-delta (Figure 54)
3
The GFX4-IR T40 can control a three-phase load star without neutral (Figure 47)
4
The GFX4-IR T40 can control a three-phase transformer (Figure 48)
5
The GFX4-IR T40 can NOT control all kind of single-phase loads or three-phase with neutral (Figure 40 - Figure 41 - Figure 42 -
Figure 43 - Figure 44 - Figure 45 - Figure 49)
80404L_MHW_GFX4-IR_03-2020_ENG
Dip 4
Dip 5
ON
OFF
Id
Id =
V = line voltage
Id = load current
P = total power
if resistive load cosj = 1
P
__________
V cosj
37