Connection Example: Power Section - gefran GFX4-IR Series Installation And Operation Manual

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

3.10
c
onnection example
Figure 40
Connection example for 4 single-phase loads, single-phase line L1-L2/N
Dip-Switches configurations
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE: Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
Figure 41
Connection example for 4 single-phase loads, 3-phase line without neutral
Dip-Switches configurations
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE: Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
80404L_MHW_GFX4-IR_03-2020_ENG
: p
ower section
Dip 4
Dip 5
OFF
OFF
Dip 4
Dip 5
OFF
OFF
P
Id = ___
V cosj
V = phase voltage (line L1 - line L2/N)
P = power of each single-phase load
Id = load current
if resistive load cosj = 1
P
Id = ___
V cosj
V = phase voltage (line L1 - line L2/N)
P = power of each single-phase load
Id = load current
if resistive load cosj = 1