Using Port 1 "Modbus Rtu; Autobaud Port 1" Procedure - gefran GPC 40-600A Use And Installation Manual

Advanced power controllers
Table of Contents

Advertisement

5.
A network typically has a Master that "manages" communication by means of "commands," and Slaves that carry out
these
commands.
GPC should be considered as a Slave to the network Master, which is normal a supervisory terminal or a PLC. It is uniquely
identified by a node address (ID) set on the rotary switches (tens + units). Up to 99 GPC modules can be installed in a serial
network, with node address selectable from '01' to '99'. The use of the letters (A...F) on the rotary switches is reserved.
GPC has a Modbus RTU serial port (PORT 1) an optional serial port (see ordering code) for the Fieldbus (PORT 2). The
Fieldbus can use one of the following protocols: Modbus RTU, Profibus DP, CANopen, Profinet, Ethernet/IP and Ethernet
Modbus TCP.
PORT 1, the Modbus RTU port, has the following factory settings (default):
The use of the letters (A...F) on the rotary switches is re-
served.
5.3.1.

"AutoBaud Port 1" procedure

The AutoBaud procedure allows the correct BaudRate
value to be set automatically by detecting the Master's
transmission frequency.
This procedure is essential for the correct use of the PORT
1 Modbus RTU port. The serial communication speed and
parity of the GPC modules must always be adjusted to the
connected supervision terminal or PLC.
AutoBaud is executed on the GPC as follows:
1.
Connect the serial cables to all modules in the network
on PORT 1 and to the supervision terminal.
2.
Set the rotary switch on the GPC modules to be
installed, or on all modules present in case of first
installation, to position "0+0".
3.
Check that the green "STATUS" LED flashes at a high
frequency (10 Hz).
4.
The supervision terminal must send a series of generic
"MODBUS" read messages to the network.
5.
The procedure is complete when all the green L1
"STATUS" LEDs on the GPC modules flash at a normal
frequency (2 Hz). NOTE: The frequency is valid if pa-
rameter 197 Ld.1 is equal to 16 by default.
6.
The new speed parameter is permanently saved
in each GPC; therefore the "AUTOBAUD SERIAL"
sequence does not have to be run in subsequent
power-ups.
NOTES:
When the rotary switch is turned, the green "STATUS"
LED stays on for about 6 seconds, after which it re-
sumes normal operation and saves the address.
The green LED L1 "STATUS", mentioned in the proce-
dure, can vary its behaviour according to the parame-
terLd.1, which by default is equal to 16.

USING PORT 1 "MODBUS RTU"

Parameter
Default
ID
1
BaudRate
19.2 kbit/s ...
Parity
None
StopBits
1
DataBits
8
81900A "MHW_GPC-40/600A"_03-2021_ENG_page 80
Range
1...99
1200...115 kbit/s
Odd/Even/None
-
-
SERIAL NETWORK
INSTALLATION 1
ModBus
?
YES
NO
"AUTOBAUD" SEQUENCE
SERIAL 1
SETTING NODE
ADDRESS
OPERATIONAL
FUNCTIONING
The communication speed of the
serial network is the same as that
of the GPC.
Green 'STATUS' LED
flashing at 10 Hz

Advertisement