Cable processing

Bare cables can be connected to the transmission cable terminal block; however, for safety reasons, it is recommended to
connect cables using bar solderless terminals.
Use UL-listed solderless terminals and, for processing, use a tool recommended by their manufacturer.
Type
Model
Bar solderless
AI 0,75-8 GY
*1
terminal
AI 1,5-8 BK
AI-TWIN 20,75-8 GY
AI-TWIN 21,5-8 BK
*1 When connecting two cables to one terminal, connect the two cables together to the TWIN bar solderless terminal.
*2 When TWIN bar solderless terminals are used, the maximum wire diameter is 1.25mm

Wiring precautions

Precautions of wiring in the AnyWireASLINK system are as follows.
• In the AnyWireASLINK system, signals and power are supplied to a slave module with two types of transmission cables;
DP and DN. Therefore, it is recommended to use a stranded wire of 1.25mm
• Wires such as general-purpose wires, cabtyre cables, and flat cables can be used.
• Do not run multiple transmission cables (DP, DN) using a multicore cable. Running multiple transmission cables (DP, DN)
together may cause noise, resulting in a malfunction.
DP
DN
DP
DN
• The voltage should not fall below the lower limit of the allowable voltage range due to the voltage drop caused by the cable.
If the voltage falls below the lower limit, malfunctions may occur.
• Do not connect soldered cables directly to the terminals. Doing so may loosen the screws, resulting in a poor contact.
• The transmission cable terminal block needs to be removed from the bridge module when wiring to the block.
• Use a crimping tool to connect a cable to a bar solderless terminal.
• Before inserting a bar solderless terminal, check the shapes of the wire insertion opening and bar solderless terminal.
Then, insert the terminal in the correct orientation. Inserting a bar solderless terminal wider than the wire insertion opening
may damage the terminal block. ( Page 29 Cable processing)
*2
Application
2
When processing a 0.75mm
cable
2
When processing a 1.25mm
cable
2
When processing two 0.75mm
cables
2
When processing two 1.25mm
cables
DP
DN
DP
DN
Contact
PHOENIX CONTACT GmbH & Co. KG
(www.phoenixcontact.com)
2
.
2
or larger for the main cable.
4 CONNECTIONS
4.2 AnyWireASLINK Side Terminal Block
4
29