AnyWireASLINK test mode

This function operates the AnyWireASLINK system connected to the bridge module separately from CC-Link to check the
system start-up or operation.
Following items can be checked when the system is not connected to CC-Link
• Wiring check on AnyWireASLINK side
• Address and parameter setting of the slave module
• Performing the automatic address detection ( Page 54 Performing the automatic address detection)
*1 Communication with CC-Link is not available during the AnyWireASLINK test mode.
*2 Do not start the AnyWireASLINK test mode when a LED of CC-Link side is on.
*3 AnyWireASLINK test mode cannot be started when system is connected to CC-Link because it automatically starts to communicate with
CC-Link.
*4 The address writer is required for settings of the slave module. ( Page 51 Settings of Slave Module)
Starting AnyWireASLINK test mode
1.
Power on the bridge module without connecting to CC-Link.
2.
Press the SET switch (first time)
Check that only the LINK LED is on and press the SET switch until the SET LED turns on.
3.
Press the SET switch (second time)
Check that the LINK LED and SET LED are on and press the SET switch again until the ALM LED turns on.
4.
Press the SET switch (third time)
Check that the LINK LED, SET LED, and ALM LED are on and press the SET switch again until the LINK LED flashes.
5.
AnyWireASLINK test mode is successfully started if the LINK LED is flashing and the SET LED and ALM LED are off.
However, if an error occurs on the bridge module, LED status indicates the error.
Exiting AnyWireASLINK test mode
Exit the AnyWireASLINK test mode by powering off and on the bridge module.