TRANSMISSION TIME
9.1

CC-Link Transmission Time

For transmission time of the CC-Link side, refer to the user's manual for the master module used.
9.2

AnyWireASLINK Transmission Time

Transmission cycle time of the bridge module
The transmission cycle time is the time required for the bridge module and all the slave modules to update I/O data.
Transmission cycle time of the bridge module is as follows.
Number of transmission points
128 points (input: 64 points, output: 64 points)
256 points (input: 128 points, output: 128 points)
384 points (input: 192 points, output: 192 points)
512 points (input: 256 points, output: 256 points)
Effects of the double check system
■Input
Unless the same data is received twice successively on the bridge module side, the input area data is not updated. A
minimum of one-transmission cycle time and a maximum of two-transmission cycle time are required for the data response.
Therefore, when input signal is shorter than two-transmission cycle time, the input data may not be captured depending on
the timing.
To ensure the response, provide an input signal that is longer than two-transmission cycle time.
Minimum data
response time
Maximum data
response time
■Output
As the double check is performed on the slave module side, the time required is the same as that for input, namely a minimum
of one-transmission cycle time and a maximum of two-transmission cycle time.
9 TRANSMISSION TIME
94
9.1 CC-Link Transmission Time
Sampling timing
Minimum of one transmission cycle time
Input data change
Sampling timing
Maximum of two transmission cycle times
Input data change
One transmission cycle time
3.6ms
6.0ms
8.3ms
10.7ms
Sampling timing
Input data update
Sampling timing
Sampling timing
Input data update