B289SB-01AK-CAM20
B289SB-01AK-CAS
8 FUNCTIONS
80
8.2 Function Details
Device parameter
Description of device parameters
Device parameter 1
Threshold value
Specify a threshold value which determines on/off of the
sensor.
Default value: 50
Setting range: 0 to 100
Device parameter 2
Hysteresis value
Specify a hysteresis value for the threshold value.
Default value: 5
Setting range: 0 to 100
Device parameter 3
Alarm determination upper limit value
Specify an alarm determination upper limit value.
Default value: 80
Setting range: 0 to 100
Device parameter 4
Alarm determination lower limit value
Specify an alarm determination lower limit value.
Default value: 20
Setting range: 0 to 100
Device parameter 5
Alarm determination monitoring time
Specify the monitoring time for the alarm determination
value.
Default value: 50 (Unit: 100ms)
Setting range: 3 to 255
Device parameter 6
Normally open setting/ normally close setting
Default value: 0
Setting value: 0 (Normally-open contact), 1 (Normally-
close contact)
Device parameter 7
Operation mode setting
Specify the use of the alarm diagnostics function.
Default value: 0
Setting value: 0 (Diagnostics function not used), 1
(Diagnostics function used)
Device parameter 8
Sensor type setting
Specify a value according to the sensor of the
manufacturer used.
Default value: 0
For setting values, refer to the manual for the slave module
used.
Device parameter 9
Specify whether to perform interference prevention for the
sensor. (The detection distance is reduced by half.)
Default value: 0
Setting value: 0 (Normal mode (no interference
prevention)), 1 (Interference prevention mode)
Device parameter 10
Device parameter 11
Device parameter 12
Device parameter 13
Read/Write
Read/Write