■How to recover from Parameter access target module ID error
1.
Eliminate the error cause such as a parameter access program.
Even when Parameter access target module ID error is cleared, the following status is maintained.
• ON state of Slave module alarm signal (RX(n+1)0)
• The value 012EH stored in Latest error code storage area (RWrn+16)
• The value 0FFFH stored in Latest error ID storage area (RWrn+17)
• The error ID stored in Latest error ID simple information (RXn6 to RXnF)
*1 If multiple errors occur simultaneously, the latest error is displayed.
*2 This applies only when the CC-Link operation mode is Ver.2.00.
2.
Power off and on the AnyWireASLINK system or turn on and off Error reset request flag (RY(n+D)A).
The following status is resulted:
• Slave module alarm signal (RX(n+1)0) turns off.
• The value in Latest error code storage area (RWrn+16) is cleared.
• The value in Latest error ID storage area (RWrn+17) is cleared.
• The value in Latest error ID simple information (RXn6 to RXnF) is cleared.
■How to recover from Parameter value error
How to recover from Parameter value error is as follows.
1.
Eliminate the error cause such as a parameter access program.
Even when Parameter value error is cleared, the following status is maintained.
• ON state of Slave module alarm signal (RX(n+1)0)
• The value 012FH stored in Latest error code storage area (RWrn+16)
• The error ID stored in Latest error ID storage area (RWrn+17)
• The error ID stored in Latest error ID simple information (RXn6 to RXnF)
• The alarm information is notified from the bridge module to the device of the CPU module.
*1 If multiple errors occur simultaneously, the latest error is displayed.
*2 This applies only when the CC-Link operation mode is Ver.2.00.
2.
Power off and on the AnyWireASLINK system or turn on and off Error reset request flag (RY(n+D)A).
The following status is resulted:
• Slave module alarm signal (RX(n+1)0) turns off.
• The value in Latest error code storage area (RWrn+16) is cleared.
• The value in Latest error ID storage area (RWrn+17) is cleared.
• The value in Latest error ID simple information (RXn6 to RXnF) is cleared.
• The alarm information that was notified to the device of the CPU module is cleared.