Ac Line Input Specifications For Xtr 850 Watt - Xantrex XTR6-110, XTR8-100, XTR12-70, XTR20-42, XTR33-25, XTR40-21, XTR60-14, XTR80-10.5, XTR100-8.5, XTR150-5.6, XTR300-2.8, XTR600-1.4 Operating Manual

Xtr 850 watt and 1700 watt series programmable dc power supply
Hide thumbs Also See for XTR6-110, XTR8-100, XTR12-70, XTR20-42, XTR33-25, XTR40-21, XTR60-14, XTR80-10.5, XTR100-8.5, XTR150-5.6, XTR300-2.8, XTR600-1.4:
Table of Contents

Advertisement

Table C-1 XTR 850 Watt Electrical Specifications for 6 V to 600 V Models
Models
6-110
11
75/77%
Efficiency
1.Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
2.Minimum current is guaranteed to maximum 0.4% of the rated output current.
3.Total output power is also based on AUX1 Output Voltage (5 V) and AUX1 Output Current (0.5 A) and AUX2 Output Voltage (15 V) and AUX2 Output Current (0.5 A).
4.From 85–132 Vac or 170–265 Vac, constant load.
5.From 85–132 Vac or 170–265 Vac, constant load.
6.From no load to full load, constant input voltage.
7.For load voltage change, equal to the unit voltage rating, constant input voltage.
8.For 6 V models the ripple is measured at 2–6 V output voltage and full output current. For other models, the ripple is measured at 10–100% output voltage and full output current.
9.When using remote sense, the total of the load voltage and the load line drops must not exceed the rated output of the power supply. For example, for an XTR 6-110 in an application
with 1 V of load line loss (0.5 V/Line), the maximum available load voltage would be 6–1= 5 V. Note: The unit may operate at higher output voltages than this, but there is no
guarantee that the power supply will meet performance specifications. Ultimately, the upper limit of the output voltage will be determined by internal circuitry of the power supply
(non-adjustable.)
10.With rated, resistive load.
11.At 100/200 Vac input voltage and maximum output power.
Applies to all footnotes: Programming and Readback: RS-232, RS-485, USB built in. GPIB, Ethernet optional.
Specifications are guaranteed from 1% to 100% of the rated output voltage, current, and power.

AC Line Input Specifications for XTR 850 Watt

The input to the power supply requires the following input specifications.
Rated AC Input Voltage/Frequency
Operational AC Input Voltage/Frequency
Input Current (at 100/200 Vac)
Inrush Current (100/200 Vac)
Power Factor Correction
8-100
12-70
20-42
33-25
77/80%
81/84%
82/85%
83/86%
100–240 Vac, 50–60 Hz
85–265 Vac continuous, single phase, 47–63 Hz
11.5/6 A
Less than 25 A
0.99@100/200 Vac, rated output power
40-21
60-14
80-10.5
100-8.5
83/87%
83/87%
83/87%
83/87%
150-5.6
300-2.8
600-1.4
83/87%
83/87%
83/87%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents