Remote Operation
Table C-3 Remote Operation
Programming Mode
Voltage and Current Output Voltage Programming
Current Output Resistor Programming
Voltage Output Resistor Programming
Output Voltage and Current Monitor
Voltage Programming Accuracy (mV)
Current Programming Accuracy (mA)
Voltage Readback Accuracy (mV)
Current Readback Accuracy (mA)
Isolation (Prog and Readback Lines)
Voltage and Current Programming Resolution
Voltage and Current Readback Resolution
Parallel Operation
Series Operation
Constant Voltage (CV)/Constant Current (CC) Indicator
APG
ISOL
0–100%, 2~ up to 10 V, programmable
0–100%, 2~ up to 10 kΩ, programmable
0–100%, 2~ up to 10 kΩ, programmable
0–100%, 2~ up to 10 V, programmable
± 0.5% of rated output voltage
± 1% of rated output current
± 1% of rated output voltage
± 1% of rated output current
With respect to chassis potential:
With respect to:
500 V
chassis potential: 500 V.
negative or positive main output: 1500 V.
negative or positive auxiliary output:
300 V.
Up to 4 units in master/slave
mode
Up to 2 units (with external
diodes)
CV: TTL High (4–5 V)
CC: TTL Low (0–0.6 V)
Digital
±0.1% of rated output voltage
±0.2% of rated output current
±0.1% of rated output voltage
±0.2% of rated output current
0.012% of full scale