Specifications and Characteristics

AC Line Input Specifications

AC Line Input Specifications
The input to the power supply requires the following specifications.
AC Line Input
Voltage
Operating
Ranges
Table E.9AC Line Input Specifications
Operating Range
Frequency Range
Maximum Peak In-rush Current at turn on 35 A
Minimum Power Factor
Operating Current
Operating Current
1. At nominal input voltage and maximum power
2. At 190V
3. At 208V
4. At 342V
5. At 400V
236
nominal 208V
(Standard)
rms
nominal 400V
(with HV-Input option)
rms
1
nominal 208V
(Standard)
rms
nominal 400V
(with HV-Input option)
rms
nominal 208V
(Standard)
rms
2
Maximum
3
Typical
nominal 400V
(with HV-Input option)
rms
4
Maximum
5
Typical
input voltage, 55
ac
input voltage, 25
ac
input voltage, 50
ac
input voltage, 25
ac
190 to 242 V
ground)
342 to 500 V
ground)
47 to 63 Hz
rms
70 A
rms
0.95
0.9
24 A (6000 Watt)
48 A (12000 Watt)
20 A (6000 Watt)
40 A (12000 Watt)
13 A (6000 Watt)
26 A (12000 Watt)
11 A (6000 Watt)
22 A (12000 Watt)
°
C ambient temperature and maximum power
°
C ambient temperature and maximum power
°
C ambient temperature and maximum power
°
C ambient temperature and maximum power
Operating Manual for XDC Series Power Supply
3 φ (3 wire + safety
ac
3 φ (3 wire + safety
ac
(6000 Watt)