Power Supply Concept - WAGO 750-585/040-000 Manual

2ao 0-20ma ex i xtr, 2-channel analog output; 0-20 ma; intrinsically safe; extreme for wago i/o system 750 xtr series
Table of Contents

Advertisement

WAGO I/O SYSTEM 750 XTR
750-585/040-000 2AO 0-20mA Ex i XTR
Pos: 31 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 2/Einspeisekonzept - Überschrift 2 @ 9\mod_1292323902755_21.docx @ 67445 @ 2 @ 1
6.2

Power Supply Concept

Pos: 32.1 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Warnung/Warnung: Ex i Einspeisung nur mit 750-606 XTR @ 28\mod_1486131251915_21.docx @ 405250 @ @ 1
Ex i XTR I/O modules shall only be supplied via "Power Supply 24 VDC
Diagn for Ex i XTR Modules"
Ex i XTR I/O modules shall only be operated with a "Power Supply 24 VDC
Diagn for Ex i XTR Modules" 750-606/040-000.
Pos: 32.2 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Warnung/Warnung: Anforderungen an Luft- und Kriechstrecken (XTR Ex i) @ 36\mod_1579514444035_21.docx @ 572089 @ @ 1
Requirements for Clearances and Creepage Distances
For all sections of a node that contain I/O modules for Ex-i use, stricter require-
ments with regard to clearances and creepage distances apply.
Before such a node section, the respective Power supply 24 VDC Diagn
for Ex i XTR Modules (750-606/040-000) ensures the required distance.
After such a node section, 4 Distance Modules XTR (750-616/040-000)
must be used.
Exception: If the following section consists only of an End Module XTR
(750-600), no distance modules are required.
Pos: 32.3 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Achtung/Achtung: Maximaler Strom Ex i Einspeisung 750-0606/040-000 XTR @ 28\mod_1486128985806_21.docx @ 405244 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current available from the "Power Supply 24 VDC Diagn for Ex i
XTR Modules" 750-606/040-000 is 1 A.
When configuring the system, ensure that this current is not exceeded.
If exceeded, an additional 750-606/040-000 must be used.
Pos: 32.4 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Hinweis/Hinweis: Ex i Luft- und Kriechstrecken einhalten XTR @ 36\mod_1579514654161_21.docx @ 572093 @ @ 1
Keep the air and creep distances between intrinsically safe segments!
The maximum current available from the 750-606/040-000 "Power Supply
24 VDC Diagn for Ex i XTR Modules" is 1 A.
If the use of further 750-606/040-000 is necessary for reasons of extent of
utilization, 4 Distance Modules XTR (750-616/040-000) must be used to
guarantee the distance between the intrinsically safe segments.
Pos: 32.5 /Serie 750 (WAGO I/O SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Information/Information: Allgemeine Informationen zu Ex i @ 4\mod_1241507736531_21.docx @ 32301 @ @ 1
Further information about explosion prevention!
Further information about explosion prevention can be found in section "Use in
Hazardous Environments"!
Pos: 32.6 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Einleitung/Versorgung/Versorgung 24 V, 0 V über Leistungskontakte Ex i XTR - NEUE FORMULIERUNG @ 28\mod_1486132138923_21.docx @ 405256 @ @ 1
The Ex i XTR I/O module (750-585/040-000) receives the 24 V voltage supply
potential and the 0V potential for the field level from an upstream Ex i XTR I/O
Connect Devices