Use in Hazardous Environments
Table 27: Description of Marking Example According to ATEX and IECEx
Marking
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Dust
II
3 D
Ex
tc
IIIC
T135°C
Dc
Mining
I
M2
Ex
d
I
Mb
Gases
II
3 G
Ex
nA
IIC
T4
Gc
Pos: 37.7 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.1.0
WAGO I/O SYSTEM 750 XTR
750-585/040-000 2AO 0-20mA Ex i XTR
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22)
Explosion protection mark
Type of protection: Protection by enclosure
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment group: Mining
Category: High level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Explosion group for electrical equipment for
mines susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2)
Explosion protection mark
Type of protection: Non-sparking equipment
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)