22
Device Description
Pos: 18.26 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 2/Technische Daten - Überschrift 2 @ 3\mod_1232967587687_21.docx @ 26924 @ 2 @ 1
3.6

Technical Data

Pos: 18.27.1 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Technische Daten/VS (Variablensteuerung)/Technische Daten Gerät (VS) - XTR @ 15\mod_1369311215011_21.docx @ 120260 @ 3 @ 1
3.6.1

Device Data

Table 7: Technical Data – Device
Width
Height (from upper edge of DIN-rail)
Depth
Weight
Degree of protection
Pos: 18.27.2 /Serie 750 (WAGO I/O SYSTEM)/Gerätebeschreibung (alte Struktur)/Technische Daten/AO/Technische Daten 750-0585/040-000 @ 28\mod_1487757272323_21.docx @ 408865 @ 333 @ 1
3.6.2

Power Supply

Table 8: Technical Data – Power Supply
Supply voltage, field
Current consumption, field supply
Current consumption, system supply
Power consumption P
Power loss P
Isolation
Rated surge voltage
Current via power jumper contacts
3.6.3

Outputs

Table 9: Technical Data – Outputs
Number of Outputs
Signal type
Signal characteristic
Load Impedance
Linearity
Resolution
Conversion time
Measurement/output error (25 °C)
Temperature coefficient
Manual
Version 1.1.0
max.
l
WAGO I/O SYSTEM 750 XTR
750-585/040-000 2AO 0-20mA Ex i XTR
24 mm
60.6 mm
100 mm
89.7 g
IP20
24 VDC via power jumper contacts
(Ex i XTR power supply: U
26.8 V)
19 mA + load (2 × 20 mA)
21 mA
1.5 W
0.9 W
300 VAC system/supply
1 kV; rated surge voltage between
intrinsically safe and non-intrinsically
safe circuits: 1.5 kV (EN 60079-11)
1000 mA
max
2
0 ... 20 mA
Single-ended
< 500 Ω
± 2 LSB
12 bits
< 2 ms
< ± 0.2 % of the largest
measurement/output area
< ± 0.01 %/K of the largest
measurement/output area
= max.
o