2ao 0-20ma ex i xtr, 2-channel analog output; 0-20 ma; intrinsically safe; extreme for wago i/o system 750 xtr series
Table of Contents

Advertisement

WAGO I/O SYSTEM 750 XTR
750-585/040-000 2AO 0-20mA Ex i XTR
Don't forget the bus end module!
Always plug a bus end module 750-600/040-000 onto the end of the fieldbus
node! You must always use this bus end module at all fieldbus nodes with the
WAGO I/O SYSTEM 750 XTR fieldbus couplers/controllers to guarantee proper
data transfer.
Pos: 26.6 /Serie 750 (WAGO I/O SYSTEM)/Montieren/Demontieren/I/O-Module 750xxxx/0040xxxx 4g-5g @ 15\mod_1367558844291_21.docx @ 118470 @ @ 1
For vibration loads > 4g, observe the following installation instructions:
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
Make the open conductor length between strain relief and wire connection
as short as possible.
Use the reinforced end stop 249-197.