Honeywell HON R100NG Series User And Maintenance Manual page 55

Gas pressure regulator with pilot
Table of Contents

Advertisement

User manual for HON R100 gas pressure regulator with HON P095NG pilot 
Figure 
Step 
Description 
13 
Take the guide bush. Replace the O‐rings 
(1, 2, 3) with new, lubricated O‐rings. 
14 
Insert the guide bush (2) back into the 
body. Make sure it is in its correct installa‐
tion position. The opening on the side 
must point towards the gas inlet side. 
Make sure not to damage the O‐rings 
when inserting the sliding bushing. 
15 
Secure the guide bush (2) with the hold 
screw (1). The hold screw needs to be 
screwed in all the way without fail. If you 
are unable to screw the hold screw in all 
the way, correct the guide bush's position 
until you are able to screw the hold screw 
in all the way. 
16 
Take the valve shank. Remove the retaining 
ring (1) below the compensating plate. 
17 
Pull the compensating plate (1) down and 
off.   
18 
Replace the O‐rings (1, 2) on the valve 
shank with new, lubricated O‐rings. 
 
Maintenance 