Operating And Measuring Lines - Honeywell HON R100NG Series User And Maintenance Manual

Gas pressure regulator with pilot
Table of Contents

Advertisement

4.3
Operating and measuring lines 
Connection lines between 
device and gas regulating 
line 
 
User manual for HON R100 gas pressure regulator with HON P095NG pilot 
The lines must be arranged and sized in such a way that the devices' intended function will be 
ensured. 
 Measuring line 
 The measuring line transmits the pressure process value from the sensing 
point to the measuring diaphragm of a controller or the pilot of a gas pressure 
regulator or safety relief valve or to the measuring diaphragm of the moni‐
toring device of a slam‐shut device. It needs to be connected to the pipe 
sideways or upwards separately for each device. In the case of safety equip‐
ment, the measuring line must be connected upstream of the first outlet‐side 
shut‐off device in such a way that it cannot be shut off. If the measuring line is 
additionally connected downstream of the first outlet‐side shut‐off device, 
3‐way ball valves with negative overlap must be used for switching. These ball 
valves do not have a valve position in which both measuring lines can be fully 
closed at the same time. 
 Vent line 
 The vent line is used to connect a measuring diaphragm to the atmosphere. If 
the measuring unit becomes damaged (e.g., diaphragm rupture), it can start 
conveying gas. Under certain operating conditions, and following consultation 
with the manufacturer, vent lines can be omitted if vent valves (HON 915) or 
safety diaphragm configurations can be used instead. 
 Blowdown line 
 The blowdown line in a safety relief valve is used to divert gas (leaking gas, 
for example) into the atmosphere.   
Grouping vent lines or blowdown lines (into a header) is permissible if it does not have a 
negative impact on the individual devices' operation. Within this context, it is recommended 
to have the cross‐sectional area of the header be at least five times as large as the total of the 
individual lines' cross‐sectional areas.   
For primary slam‐shut devices, it is recommended to route the slam‐shut devices' vent lines 
separately. Vent lines must not be grouped together with blowdown lines. 
 Discharging line 
 When using indirect acting (pilot‐operated) slam‐shut devices, the discharg‐
ing line is used to divert the exhaust gas from the pilot into the system's out‐
let chamber. On certain devices, the discharging line will be grouped with the 
feedback line.   
 Feedback line 
 When using indirect acting (pilot‐operated) slam‐shut devices, the feedback 
line is used to return the outlet pressure to the actuator. 
 
Basics for installing the device in a pipe 
 
 
29 