User manual for HON R100 gas pressure regulator with HON P095NG pilot
Figure
Step
Description
25
Turn the housing over. Replace the O‐ring
(1) with a new, greased O‐ring.
26
Put the upstream pressure stage housing
back on the second pressure stage's
housing. Make sure that the diaphragm
unit does not fall out! Tighten the screws
(1), including the washers, in a criss‐cross
sequence. Observe the tightening torque
information provided in the table before
this section.
27
Replace the stabilizer seat with a new one.
Unscrew the nut (1).
28
Insert new, greased O‐rings (1, 2). Screw
the nut back on.
29
Screw the stabilizer seat (1) back into the
housing.
Maintenance
71