Interpreting the type 
plate of the pilot 
 
2.5
Layout and operation 
Assemblies 
How it works 
User manual for HON R100 gas pressure regulator with HON P095NG pilot 
The details on the type plate have the following meaning: 
Figure 
 
The gas pressure regulator is made up of the following assemblies: 
Figure 
 
 Gas pressure regulators consisting of an HON R100NG actuator assembly combined 
with an HON P095NG pilot can be used to maintain the outlet pressure of a gas con‐
stant within set limits within a regulating line regardless of the influence of disturbance 
variables such as inlet pressure changes and/or discharge changes. 
 The outlet pressure that needs to be regulated is fed to the pilot. The diaphragm system 
in the pilot determines the pressure process value as a force on the measuring dia‐
phragm and compares it with the force of the pilot spring, which is used as reference 
variable. If control deviations are detected based on the results from this comparison, 
the opening position of the actuator assembly's regulating diaphragm will be changed 
by adjusting the motorization pressure so that the pressure being regulated (process 
value) will change to match the setpoint. When there is zero pressure flow, the device 
seals tightly. 
 
No. 
Meaning 
Manufacturer 
Name of the device 
Manufacturing date 
Setpoint range 
Specific set range 
Response pressure setpoint 
In conformity with standard, e. g., 
DIN EN 334 
CE marking 
Serial number 
10 
Customer revision No. 
11 
Maximum inlet pressure 
12 
Temperature range 
No. 
Description 
HON R100NG actuator assembly 
HON P095NG pilot 
 
Description 