Table 5-9. Controller Modules (CON0-3)
Title
Auto Status
Remote Status
Reverse Valve
Alarm A Active
Alarm B Active
Auto Switch
Remote Switch
Auto Enable
Definition
When Output Track Status (OVTS) is 0 , 1
indicates Control Output (CO) is selected as
the output. 0 indicates the output comes from
the output push buttons.
When the Setpoint Track Status (SPTS) is 0 , 1
indicates the setpoint is derived from the
Remote Setpoint (RSP). 0 indicates it comes
from the setpoint push buttons.
This parameter specifies the location of
Open/Close indicators in the control display.
1 means that 20 mA closes the valve. 0
indicates that 20 mA opens the valve.
See Control Alarm Mode (AIX).
See Control Alarm Mode (AIX).
This parameter is used in conjunction with
Auto Enable (AE) to allow the Control Output
(OUT) to become the auto/manual generator
result Output (OUT).
This parameter is used in conjunction with
Remote Setpoint Enable (RE) to allow the
modified Remote Setpoint to become the
setpoint value to the setpoint generator.
When this parameter is set to a 1 , the Control
Output (CO) becomes the auto/manual
generator result Output (OUT) if the Auto
Switch (SWA) is set to a 1 by the A/M push
button or user program (F-TRAN, FCIM, or
FCS wire list).
Atom
CON0 CON1 CON2 CON3
AUT
L107
L131
L155
(0-3)
RMT
L108
L132
L156
(0-3)
RSV
L109
L133
L157
(0-3)
PA1
L110
L134
L158
(0-3)
PA2
L111
L135
L159
(0-3)
SWA
L112
L136
L160
(0-3)
SWR
L113
L137
L161
(0-3)
AE
L114
L138
L162
(0-3)
4 of 9
Default
L179
0
L180
0
L181
0
L182
0
L183
0
L184
0
L185
0
L186
1