Table 5-14. System Module
Title
Display
This value is the current display program index number.
Program
This parameter controls the display screen intensity. For Model 53MC5000A controllers and
Display
Model 53MC5000B controllers with the Low-Res display, index values from 0 to 7 determine
Brightness
brightest (0) to dimmest (7) intensity. This parameter has negligible effect on display brightness
in 53MC5000B controller models with the Hi-Res display.
Alarm line annunciation can be inhibited. Normally when datapoint L065 is a 1, the contents of
Alarm
datapoint A009 are superimposed over the current display. If datapoint L063 is set to a 1, no
Disable
superimposing will occur.
Alarm
The value placed in this parameter will be presented at the top of the display whenever an
Line
unacknowledged alarm condition exists.
These datapoints contain the index numbers of the displays to be presented in the desired
sequence. The display list is organized such that each group of displays is made of consecutive
datapoints with one group immediately following the preceding group. The display list allows
entries for up to 8 groups with 8 displays each. Index numbers correspond to any user written
display program (see Customization Guide 53MC5000) or to the list of preprogrammed standard
displays that is provided in Section 4.
A display list example of preprogrammed standard displays for a two loop controller (CON0 and
CON1) with a locator grid that has three display groups (three columns) and three displays per
Display
group (three rows) would be as follows:
List
B21 = 1 Alarm Summary (Column 1, Row 1)
B22 = 7 Two Loop CON0 and CON1 (Column 1, Row 2)
B23 = 21 Status Module 0 (Column 1, Row 3)
B24 = 14 Parameter Module 1 (Column 2, Row 1)
B25 = 9 Single Loop CON0 with Horizontal Trend (Column 2, Row 2)
B26 = 13 Parameter Module 0 (Column 2, Row 3)
B27 = 18 Parameter Module 5 (Column 3, Row 1)
B28 = 10 Single Loop CON1 with Horizontal Trend (Column 3, Row 2)
B29 = 17 Parameter Module 4 (Column 3, Row 3)
Definition
5 of 6
Atom
Data-
De-
point
fault
DSPL
B005
3
BRGT
B012
4
NALIN
L063
0
ALINE
A009 ALARM
B021-
B084