Table 10-3. Cs5 Ratio Automatic/Manual Station Datapoints - ABB ControlIT 53MC5000 Instruction Manual

Multi-loop process controller
Table of Contents

Advertisement

Table 10-3. CS5 Ratio Automatic/Manual Station Datapoints

Data-
point
Table
Module
C256
5-4
AI0
C276
5-4
AI0
B269
5-4
AI0
L416
5-4
AI0
L440
5-4
AI0
C257
5-4
AI1
C277
5-4
AI1
B270
5-4
AI1
L417
5-4
AI1
L441
5-4
AI1
C258
5-4
AI2
C278
5-4
AI2
B271
5-4
AI2
Section 10. CS5 - Ratio Automatic/Manual Station
AI0 - Auto Input
Engineering Span - Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the Auto Input upper range
signal value.
Engineering Zero - Enter a value that represents in
engineering units the Auto Input lower range signal value.
Digital Filter Index - This is a first order filter that can be
applied to the Auto Input signal. See Table 5-4 for input
values.
0-5 V Input - Enter a value that matches the voltage range of
the Auto Input signal. 1 = 0 - 5 V range; 0 = 1 - 5 V range.
Square Root Signal - It is used if the Auto Input signal is a
squared value. 0 = input is already linear; 1 = square root to
restore linearization.
AI1 - Remote Ratio Input
AI1 Engineering Span - Set to 100 by CS5; however, it can
be changed. Enter a value, that when added to the
Engineering Zero value, will produce an upper range value in
engineering units that represents the Remote Ratio Input
upper range signal value.
Engineering Zero - Enter a value that represents in
engineering units the Remote Ratio Input lower range signal
value.
Digital Filter Index - This is a first order filter that can be
applied to the Remote Ratio Input signal. See Table 5-4 for
input values.
0-5 V Input - Enter a value that matches the signal voltage
range of the Remote Ratio Input signal. 1 = 0 - 5 V input
range; 0 = 1 - 5 V input range.
Square Root Signal - It is used if the Remote Ratio input is a
squared signal value that must be linearized. 0 = input is
already linear; 1 = square root to restore linearization.
AI2 - Alarmed Variable
Engineering Span - Enter a value, that when added to
Engineering Zero, will produce an upper range value in
engineering units that represents the Alarmed Variable upper
range signal value.
Engineering Zero - Enter a value that represents in
engineering units the Alarmed Variable lower range signal
value.
Digital Filter Index - This is a first order filter that can be
applied to the Alarmed Variable signal. See Table 5-4 for
input values.
Title and Function
1 of 3
De-
fault
100
0
3
0
0
0
0
3
0
0
0
0
3
10-5