CONTROL MODULE TAG
NAME (A000)
50 SEGMENT VERTICAL
AXIS
TREND LINE OF 40 SAMPLE
DOTS
PROCESS VARIABLE BAR
TREND INDICATOR TIME
FRAME (40 SAMPLES X 2
SEC TREND RATE = 80 SEC
TIME FRAME).
TREND RATE IS CON-0,
B336 OR TREND MODULE 0
B355). ACCEPTABLE TREND
RATES ARE 1,2,3,4,5,6,10,
12,15,20,30,AND 60 SEC. AN
INVALID VALUE CAUSES
THE NEXT LOWEST VALUE
TO BE USED. 0 = NO
TRENDING.
ENGINEERING UNITS (A001)
M = MANUAL, L = LOCAL
STATUS INDICATORS
SP = SETPOINT OR
RA = RATIO
PV = PROCESS VARIABLE
OV = OUTPUT VALUE
*PB = PUSH BUTTON
Figure 4-10. Point Displays 9 - 12, Single Loop with Horizontal Trend
4-24
53MC5000 Process Control Station
F2 - PAGE IN LIST OR PAGE FORWARD
F1 - NEXT DISPLAY GROUP OR PAGE BACK
TREND MODES (CON-0 B337 OR TREND MODULE 0 B356)
ARE AS FOLLOWS:
0 = INSTANTANEOUS VALUE. IF TREND RATE (TRR) = 2,
THEN SAMPLES AT EVERY 2ND SECOND ARE
RECORDED.
1 = AVERAGE VALUE. IF TRR = 2, THEN USE AVERAGE OF
ALL SAMPLES TAKEN FOR 2 SECONDS.
2 = MAXIMUM VALUE. IF TRR = 2, EACH SAMPLE IS TESTED
TO BE > EVERY SECOND FOR 2 SECONDS. LARGEST
IS USED IN TREND.
3 = MINIIMUM VALUE. IF TRR = 2, EACH SAMPLE IS TESTED
TO BE < EVERY SECOND FOR 2 SECONDS. SMALLEST
IS USED IN TREND.
(Sheet 2 of 2)
CON0 CONTROLLER SPAN
(C115) + CONTROLLER LOWER
RANGE (C116)
R/L - REMOTE/LOCAL
SETPOINT CONTROL PB*
L = SETPOINT UP ARROW PB
L = SETPOINT DOWN ARROW
PB
SETPOINT
AUTO/MANUAL OUTPUT
SELECTOR PB
M = DECREASE OUTPUT PB
CON0 CONTROLLER LOWER
RANGE (C116)
M = INCREASE OUTPUT PB
MODE - ALARM RESET