ABB ControlIT 53MC5000 Instruction Manual page 270

Multi-loop process controller
Table of Contents

Advertisement

Section 14. CS40 - Dual Two Loop Cascade Controller
Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints
Data-
point
Table
Module
CON0 • OUT (Setpoint from Loop 1 to Loop 3) (Cont)
C106
5-9
CON0
C107
5-9
CON0
C108
5-9
CON0
C111
5-9
CON0
C115
5-9
CON0
C116
5-9
CON0
C118
5-9
CON0
L472
5-5
AO0
L168
5-9
CON2
L170
5-9
CON2
C181
5-9
CON2
C182
5-9
CON2
C190
5-9
CON2
CON 2 #1 Secondary Control Output (LOOP 3) Related Datapoints
C178
5-9
CON2
C179
5-9
CON2
C180
5-9
CON2
Proportional Band - Is the percent of error required to move
the CON0•OUT full scale for proportional action.
Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.
Rate Time - Represents the minutes proportional action is
advanced.
Manual Reset - It determines output valve position when the
controller Loop 1 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.
Controller Span - Enter a value, that when added to the
Loop 1 Control Lower Range value, will produce the Control
upper range value in engineering units.
Controller Lower Range - Enter a value that represents in
engineering units the Loop 1 Control lower range value.
Output Slew Rate - It is a rate limit applied to the output
value (setpoint from Loop 1 to Loop 3). When configured to
a non-zero value, the output from the Loop 1 Auto-Selector is
only allowed to change by this amount each scan time. A
zero disables output slewing. It does not affect manual
operation.
AO0 - #1 Secondary Control Output (Loop 3)
0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the Loop 3 output valve requirements.
Manual Fallback Disable - 0 = always power up Loop 3 in
manual; 1 = auto/manual selector unchanged at power up.
Hard Manual Limit - 1 = apply output limits to the final output
of the Loop 3 Auto-Manual Generator. Affects both the
manual push buttons and the controller's result. 0 = do not
apply limits.
Output High Limit - Sets maximum Loop 3 output signal
value in engineering units.
Output Low Limit - Sets minimum Loop 3 output signal value
in engineering units.
Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Loop 3 Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.
Proportional Band - Is the percent of error required to move
the Loop 3 output full scale for proportional action.
Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.
Rate Time - Represents the minutes proportional action is
advanced.
Title and Function
3 of 7
De-
fault
100
0
0
50
100
0
0
0
0
1
100
0
0
100
0
0
14-9