3.3 Power Supply Specifications

Item
Input power supply voltage
Input max. power [W]
Inrush current [A]
Permissible instantaneous power
failure time [ms]
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size [mm
Applicable solderless terminal
Applicable tightening torque [N
(Terminal block terminal screw)
3 - 5
A950GOT, A951GOT-Q, A951GOT, A953GOT
By noise simulator of 500Vp-p noise volatage, 1µs noise width and 25 to 60Hz
noise frequency
2
]
cm]
Remarks
Please note that resetting will take place if an instantaneous power failure occurs to
the GOT power supply.
However, the monitoring and other functions operate normally if the instantaneous
power failure time is within 1ms.
Specifications
24VDC (+10%, -15%)
12
40 max. (30VDC, max. load)
1(19.2VDC or more)
500VAC for 1 minute across DC external terminals and earth
10M
or larger by insulation resistance tester
RAV1.25-3, V2-S3.3,V2-N3A, FV2-N3A
MELSEC-GOT
A956GOT
16
0.75 to 2
59 to 88
A956WGOT
22
3 - 5

Hide quick links: