3.3 Power Supply Specifications

Item
Input power supply voltage
Input max. power
Inrush current
Permissible instantaneous power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless terminal
Applicable tightening torque
(Terminal block terminal screw)
Remark
3 - 8
3.3 Power Supply Specifications
A950GOT, A951GOT-Q, A951GOT, A953GOT
By noise simulator of 500Vp-p noise voltage, 1_s noise width and 25 to 60Hz noise frequency
When an instantaneous power failure occurs for the time exceeding the permissible
instantaneous power failure time in the 24VDC power supply, the GOT may be reset.
In such a case, the GOT will automatically return and start communicating.
As the communication between the GOT and PLC is stopped when an instantaneous
power failure occurs, some object functions may not be performed normally.
Specifications
24VDC (+10%, -15%)
12W
40Ap, max. (26.4VDC, max. load)
1 ms (19.2VDC or more)
500VAC for 1 minute across DC external terminals and earth
10M
or larger by insulation resistance tester
0.75 to 2 mm
RAV1.25-3, V2-S3.3,V2-N3A, FV2-N3A
59 to 88 N cm
A956GOT
A956WGOT
16W
2
2
22W

Hide quick links: