6.3. Example 3. Read the VF-S15 parameter

When access to VF-S15 parameter, set "1000" to the PNU.
6.3.1.
Request data table (Read
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Address (Byte 1)
Parameter Address (Byte 2)
Parameter Address (Byte 3)
Parameter Address (Byte 4)
Parameter Address (Byte 5)
Parameter Address (Byte 6)
* Refer to section 6.5.
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-S15 parameter.
6.3.2.
Response data table (positive)
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Value (Byte 1)
Parameter Value (Byte 2)
Parameter Value (Byte 3)
Parameter Value (Byte 4)
* Refer to section 6.5.
** Value 0x31EC is "12780" in decimal. This means "127.80 (%)".
(Input voltage))
fd04
Field
Request Reference
Request ID (0x01: Request) *
Axis
Number of Parameters
Attribute
Number of Elements
Parameter number, High byte **
Parameter number, Low byte **
VF-S15 Parameter number, High byte
VF-S15 Parameter number, Low byte
Field
Request Reference (mirrored)
Response ID *
Axis (mirrored)
Number of Parameters
Format *
Number of Values
Values, High byte
Values, High byte
Description
Description
- 41 -
E6582051
Value
0x01
0x01
0x01
0x01
0x10
0x01
0x03
0xE8
0xFD
0x04
Value
0x01
0x01
0x01
0x01
0x06
0x01
0x31 **
0xEC **