Page 2
(1) The technical information provided herein describes typical operations and applications of the product and does not guarantee the intellectual property rights or other rights of Toshiba or third parties nor allows license of its use. (2) No part or the whole of this document may be reproduced without prior consent.
Page 3
Indicates Warning. Specific details are indicated near the symbol with pictures and text. Warning (Note) Descriptions of Prohibition, Mandatory Action, and Warning vary depending on the display on the main unit. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 4
Safety Precautions on Installation WARNING Ground the device. Construct the emergency stop circuit and interlock circuit Otherwise, it may cause an electric Ground Mandatory outside shock or fire. the nv series. Otherwise, it may cause an injury accident or damage to the machine if failure or malfunction occurs in the series.
Page 5
Prohibited It may cause fire or failure due to overheat. For installation and wiring of the system, observe the installation Mandatory conditions and methods Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 6
Safety Precautions on Maintenance and Inspection WARNING When installing or removing the module after wiring, make sure Mandatory that the external power supply is off. Otherwise, there will be live electric poles on the back of the external terminal block of the module, causing an electric shock.
Page 7
Mandatory with the device specifications. If not, it may cause damage of the device, or fire due to overheat, as well as not obtaining the original performance of the device. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 8
CAUTION Do not touch anything other than Do not forcefully bend, pull, or the operation part (setting twist the power cord and cables. Prohibited Prohibited switches inside the module), such It may cause breaks or heating. as the IC parts and terminals, connectors, and soldered surfaces inside the module.
Page 9
(e.g. employing fool-proof design, fail-safe design, or redundant design). Disclaimer Toshiba shall not be responsible for any damage caused by fire or earthquake, acts of a third party, other accidents, the user's willful acts or negligence, misuse, or use in abnormal conditions.
Page 10
• Unified Controller nv series TC-net 100 Module Manual (6F8C1360) (This document) Describes the TC-net 100 (TN8) module, which is common to Type 1 and Type 2 of the nv series. After reading the manual, place it in a location that can be accessed easily when necessary.
Page 11
•Chapter 6 Maintenance and inspection Describes troubleshooting regarding daily inspection and periodical inspection and how to perform inspections. •Chapter 7 Application interface Describes the user application interface and usage constraints. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
TN8 Module 1.2.2 Functions of the parts ··········································· 5 ...1 Installation (Installation to the Basic Unit) ················· 8 Chapter 2 Connecting the TC-net 100 Cable ·························· 10 Installation and Connecting the Serial Communication Port (RS-232C) Wiring Cable ································································ 12 ...7 Replacing the Module ··········································...
Page 13
Restriction on Station Redundant Configuration ······ 70 General Specifications ········································ 72 Appendix A TC-net 100 Transmission Specifications ················· 73 Specifications Function Specifications ······································· 74 ...71 Serial Communication Port (RS-232C) Transmission Specifications ···················································· 75 Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 14
Appendix B Outside Dimensions ...77 Appendix C Related Products ...79 Appendix D Decimal-hexadecimal Conversion Table ...81 6F8C1360...
Page 15
Chapter 1 Introducing the TN8 Module This chapter describes the functions, characteristics, and names and functions of the TN8 module Functions and Characteristics of the TN8 Module ··· 2 Names and Functions of the Parts ····················· 4 1.2.1 Names of the parts ·································· 4 1.2.2 Functions of the parts ·······························...
The TN8 module is a device to connect the controller main unit of the Unified Controller nv series to the information and monitoring control network TC-net 100. For the interface of the TN8 module, optical fiber cables are provided: One for single bus and one for dual-redundant bus.
Page 17
1.1 Functions and Characteristics of the TN8 Module Example of system configuration Host system network Monitoring control newwork TC-Net 100 Unified Controller nv series TC-net I/O system Figure 1-1 System configuration example (Optical transmission path) Unified Controller nv series TC-net100 (TN8) Module Operation Manual...
Serial communication port TOOL TOOL ・TOOL State display LED(A system) ・LNK-A ・ACT-A LNK-A ACT-A LNK-A ACT-A TC-net 100 modular connector for A system TN-A TN-A State display LED(B system) LNK-B ACT-B ・LNK-A ・ACT-A TN-B TC-net 100 modular connector for B System...
ON: SCAN transmission is in execution. ON during transmission OFF: SCAN transmission is under suspension. L-A (green) Displays the TC-net 100 A system state. ON: TC-net 100 transmission is in execution. OFF: TC-net 100 transmission is under suspension. L-B (green) Displays the TC-net 100 B system state (TN822 only).
Page 20
Serial communication port RS-232C (TOOL) A RS-232C port for maintenance. The connector is a 9-pin D-sub connector (socket). TC-net 100MT-RJ connectors (TN-A and TN-B) A communication port for the TC-net 100. The optical fiber cord with the MT-RJ connector is connected to it. 6F8C1360...
Page 21
This chapter describes installation and wiring methods of the TN8 module. Before installation and wiring, read this operation manual thoroughly. Installation (Installation to the Basic Unit) ··············· 8 Connecting the TC-net 100 Cable ························· 10 Connecting the Serial Communication Port (RS-232C) Cable ····························································· 12...
Chapter 2 Installation and Wiring Installation (Installation to the Basic Unit) Before installing or removing the module, WARNING make sure that the basic unit to which the TN8 Mandatory module is installed is turned off. Otherwise, it may cause an electric shock. Do not touch the interior of the product except WARNING the switches.
Page 23
After installing it to the basic unit, secure it using the screws at the top and bottom of the module. Basic unit TN8 module Module guide of the basic unit Figure 2-1 Installing to the basic unit Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 2 Installation and Wiring Connecting the TC-net 100 Cable Connect the TC-net 100 cable (optical fiber code) to the TN8 module. Before installation or wiring, remove the static CAUTION electricity from your body. Mandatory The static electricity accumulated in the human body may cause failure of the product.
Page 25
When laid fixed Optical fiber code Note • The allowable bent radius of the optical fiber cable depends on the product. Follow the manufacturer's specification of your optical fiber cable. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 2 Installation and Wiring Connecting the Serial Communication Port (RS-232C) Cable For downloading programs or performing maintenance, the serial communication port (TOOL) can be used to communicate with the tool. RS-232C is used for communication. The RS-232C cable connector is a 9-pin D-sub connector (socket). TN8 module Serial communication port (TOOL)
Turn off the basic unit. Make sure that it is off by using LED display. Unlock the connector lock in the TC-net 100 cable side connected to the module with your finger, and remove it. Loosen the screws at the top and bottom of the module with a Phillips screwdriver, and remove it along the module guide of the basic unit.
Page 28
Chapter 2 Installation and Wiring Basic unit TN8 module Module guide of the basic unit Figure 2-4 Replacing the TN8 module 6F8C1360...
Page 29
Chapter 3 Setting Switch Setting ············································· 16 3.1.1 Station address setting switch (STN-H, STN-L) ···································· 16 3.1.2 Operation mode setting switch (MODE) ······ 17 Network Parameter Setting ····························· 18 3.2.1 Network ID and subnet mask ·················· 18 3.2.2 Station address ··································· 19 3.2.3 Overview of multicast address ··················...
3.1.1 Station address setting switch (STN-H, STN-L) The station address setting switches are hexadecimal rotary switches that determines the station address on the TC-net 100 network. For setting of the IP address, refer to "3.2 Network parameter setting." Set the station address (1 to 254) that has been assigned upon system configuration in a HEX code.
"nv series 1" is the standard. "nv series 2" is used for expansion. Do not use it normally. Tool setting is used to use network parameters set by the engineering tool. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
2 setting Use the operation mode setting switches to set the IP address type to "nv series 2." This setting is used for expansion of the TC-net 100, and not used normally. Network ID: 172.31.64.XX (XX indicates the value of the station address setting switches) Subnet mask : 255.255.192.0...
3.2.3 Overview of multicast address The TN8 module supports 15 multicast addresses. Support addresses are as follows: Table3-3 Multicast address Multicast address 225.224.0.1 225.224.0.2 225.224.0.3 225.224.0.4 225.224.0.5 225.224.0.6 225.224.0.7 225.224.0.8 225.224.0.9 225.224.0.10 225.224.0.11 225.224.0.12 Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 34
Chapter 3 Setting 225.224.0.13 225.224.0.14 225.224.0.15 Any of the 15 addresses can be selected and registered by using one TN8 module. Registration to the TN8 module is performed with the engineering tool. For the registration method, refer to "3.3 Setting with the engineering tool."...
"Unified Controller nv series Type 1 Function Manual" (6F8C1221) or "Unified Controller nv series Type 2 Function Manual" (6F8C1362). Note • The switch setting becomes effective from the next startup. Restart the controller after setting. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 3 Setting 3.3.1 Network parameter setting Set the network parameters of the TN8 in the following steps. Select the TN8 module from the product tree. Select [Station] under the created system, and select [New (W)] from [File (F)] on the menu bar. Figure 3-3 Station registration screen Set the station name.
Page 37
Unit registration screen Add the module to the unit. Select [Module] under the unit, and select [New (W)]. Select "TN8 module" from the module addition dialog. Figure 3-6 Module registration screen Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 38
Chapter 3 Setting Select the added TN8 module. When [Module parameter] is selected from [File (F)] on the menu bar, the module parameter screen is displayed. Figure 3-7 An example of module registration 6F8C1360...
Page 39
V series Standard 1 sets all of the operation mode setting switch Bit 7 to 8 of the TN8 module to OFF. IP address: 172.16.64.xx ("xx" indicates the value of the station address setting switch.) Subnet mask: 255.255.192.0 Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 40
Chapter 3 Setting V series Standard 2 sets the operation mode setting switch Bit 7 of the TN8 module to ON and the operation mode setting switch Bit 8 to OFF. IP address : 172.16.64.xx (xx indicates the value of the station address setting switches) Subnet mask : 255.255.192.0 The Arbitrary setting sets the operation mode setting switch Bit 7 of the...
Page 41
[Primary (P)] and [Secondary (S)] from [Transmission target]. Restart it. The downloaded information becomes effective at the next startup. After the download is complete, restart it. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 42
Chapter 3 Setting From the product tree, set the network. Select the network under the system, and select [New (W)]. Figure 3-10 Network registration screen Select [TC-net 100LAN] from the network addition dialog. Select the module under the selected [TC-net 100LAN], and then select [New (W)].
Page 43
Network module registration screen Connect to [TC-net 100LAN]. The TN8 module added previously is displayed on the module addition dialog. Selecting it connects it to TC-net 100LAN. Figure 3-13 Network module addition dialog Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 44
Chapter 3 Setting Figure 3-14 TC-net 100LAN connection screen Connect the engineering tool to the serial communication port (TOOL) of the TN8 module to obtain the information of the current TN8 module. From [Options (O)] in [Hardware Configuration] of the configuration editor, click [Transmission Parameter (T)] to set the transmission parameter.
Page 45
Figure 3-15 Transmission parameter setting screen After the registration is complete, check that the information of the TN8 module can be read. Figure 3-16 An example of reading TN8 module information Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 3 Setting 3.3.2 Setting the scan sending blocks Set the scan sending blocks from the product tree. Select the scan memory of the TC-net 100LAN, and then select [Sending Block]. Figure 3-17 Scan sending blocks reading screen Register each of the blocks. Register each of the blocks.
Page 47
The transmission speed and information about the slot in which the output controller using the block are displayed for the registered scan sending block. Figure 3-20 Parameter screen of Sending blocks Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 48
Chapter 3 Setting Download the registered data to the TN8. After checking the data, download it to the TN8 module. To download, display the parameter information, and select [File (F)]->[Download (D)]. Note • If the controller is in a redundant configuration, the module parameters of the TN8 can be downloaded independently by selecting [Primary (P)] and [Secondary (S)] from [Transmission target].
Note ・Setting register “Yes” for status change detection, “Point No.” is downloaded to TN8 module in the carry. “Point No.” outputted by GET_IFP_INF command becomes “Point No.” from TN8 module. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 50
Chapter 3 Setting Download the registered data to the TN8. After checking the data, download it to the TN8 module. To download, display the parameter information, and select [File (F)]->[Download (D)]. Note • If the controller is in a redundant configuration, download the module parameters of the TN8 by selecting [Primary (P)] and [Secondary (S)] from [Transmission Destination].
Page 51
TN8 module or controller + 3 module. + 4 Status change + 5 Bit history + 6 Status change Data + 7 + 8 IP task No. +9 Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 3 Setting Network Information 3.4.1 Referring to LAN transmission map Display LAN transmission map In the system view, select the TN8 module, and select [LAN transmission map (S)] from [Tool (T)] on the menu bar. Figure 3-24 LAN transmission map selection screen Display talker state and healthy state Click “Start”...
After clearing the overlapping state, check that the operation is normal. The overlapping sending map retains the state once the overlapping sending state is detected. Therefore, to confirm the state recovery, clear the overlapping sending SA (station address). Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 54
Chapter 3 Setting Click [Stop] on the monitor. Select [Clear Overlapping Sending SA] to clear the overlapping sending SA (station address). 6F8C1360...
(N)] from [Tool (T)] on the menu bar. Figure 3-27 LAN management information selection screen Displayed is the information on each node connected to TC-net 100LAN . Figure 3-28 LAN management information screen Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 3 Setting 3.4.6 Detailed explanation of LAN management information When [Detailed explanation (D)] in the LAN management information screen is clicked, each detailed counter is displayed. Figure 3-29 Detailed explanation of LAN management information 6F8C1360...
When [MIB information (M)] in the LAN management information screen is clicked, the details of MIB information are displayed. Remark • MIB: Management Information Base Figure 3-30 MIB information screen Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 3 Setting 3.4.8 Reception system switching Select Reception system of TC-net 100(Normally receive automatically). When [Reception switching (X)] in the LAN management information screen is clicked, the configuration dialog is displayed. Figure 3-31 TC-net 100 reception switching screen 3.4.9 Viewing the in-ring map The in-ring map displays the nodes that currently belong to the TC-net 100.
Continuously unhealthy Talker area of Other node is normal: Always unhealthy other node Healthy Other node is abnormal: Unhealthy Figure 3-33 shows an example of the self healthy mode configuration. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 60
Chapter 3 Setting (1) one-unit (2) two-unit configuration configuration JTNI Cable Figure 3-33 An example of the self healthy mode configuration Remark • If an error occurs in the host controller after an error occurs in the transmission path, the scan block set for the host controller becomes unhealthy.
The scan talker block must be set in the host controller making the scan sending start request. Important • Do not write to this block from the application. Table 3-5 shows the information configuration of the RAS information block. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 62
Chapter 3 Setting Table 3-5 Information configuration of RAS information block Word Update Remark cycle Install information of the Module Type (0x23) target controller(*1) TN8 healthy counter 0.1s Slot 0 healthy counter 0.1s Slot 1 healthy counter 0.1s Slot 2 healthy counter 0.1s Slot 3 healthy counter 0.1s...
Page 63
Chapter 4 Operation This chapter describes the operations of the TN8 module, such as checking before operation, startup, and shutdown.
Page 64
"Table 1-1 Display details on the state display LED and normal display" on page 5. If the module doesn't start up or if the operation is erroneous, stop using the product immediately and contact one of Toshiba's service representatives. Shutdown operation To shut down, turn off the power of the power supply module.
Page 65
Chapter 5 Troubleshooting This chapter describes troubleshooting for the TN8 module.
Make the setting value - alternately station address unique in the system. setting switch TC-net 100 Blinking at the Blinking TC-net 100 Make them match with parameter same time parameters do not the engineering tool. mismatch match other node currently in...
Page 67
Chapter 6 Maintenance and Inspection This chapter describes maintenance and inspection such as daily inspection, periodical inspection, and cleaning of TN 8 module. Inspection ···················································· 54 6.1.1 Daily inspection ··································· 54 6.1.2 Periodical inspection ····························· 55 Life Limited Parts ·········································· 55...
<TC-net 100 connector> Check the following: • Cable connection is normal. • The modular connector is locked. • Cable connection is not loose or has an abnormal appearance. If any abnormality is found, contact one of Toshiba's service representatives. Ventilation hole 6FE8C1360...
Page 69
Check the front panel and upper ventilation hole of the product for dust or stain. If the ventilation hole is blocked by dust or stain, remove the dust with a vacuum cleaner, and then wipe it with a soft cloth. Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Toshiba's service representatives. Life Limited Parts To use the product safely for a long time, replace the life limited parts regularly. When replacing them, consult with one of Toshiba's service representatives. The following table shows the life limited parts and their replacement cycles.
Page 71
6.2 Life Limited Parts Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 72
Chapter 7 Application Interface This chapter describes information by socket, transmission path diagnosis information, TN8 module state information, and usage constraints of the application interface. Information by Socket ·································· 59 7.1.1 Configuration of information by socket ········ 59 7.1.2 Referring to information by socket ············ 60 7.1.3 Timing of generation of information by socket ··...
Page 73
Chapter 7 Application Interface The TN8 module expands the state information by socket used by the user application as well as diagnosis information of the transmission path to the TN8 modules within the same network on the station bus. Different is the address on the station bus expanding each state information.
Chapter 7 Application Interface The base address of the station bus address varies depending on the slot where the TN8 module is installed. The following table shows the starting word addresses of the information by socket when the TN8 module is installed to different slots. Table 7-2 Slots and station bus addresses Beginning of single Base address...
(Note) When running the controller and then halting it, close is requested by the controller basic software for the socket used by the controller. Figure 7-3 Information by socket and clear timing (1) Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 77
Chapter 7 Application Interface The timing of setting and clearing bit information of information by socket is shown below. Information by socket ソケット単位情報 Passive パッシブ <TCP> <AOP> <POP> <CON> <RCV> <RCL> Open Reception Close オープン 受信 クローズ request request request 要求...
Chapter 7 Application Interface 7.2.2 Configuration of the scan data unhealthy map The scan data healthy map is managed in the configuration as shown in Figure 7-6. The scan data healthy map shows the state history information of the corresponding scan data blocks. Bit “1”...
Chapter 7 Application Interface 7.2.4 Configuration of RAS information In the RAS information area, the information for all nodes is shared. The state information of each node is updated periodically, which consists of 64 words per node. The configuration information depends on the node type. The information of each node is expanded at the position of the station number x 128 bytes from the beginning of the RAS information area by 64 words.
Page 82
A0 is Stack 0 of A system HUB 。 (Note 2) : Number of received packets has number of each port normal packets in 16 bits. It transits in 65535→0→1→2... Figure 7-9 Configuration of RAS information on HUB Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
TC-net 100. The in-ring map shows the stations that are currently on the network. If an error occurs in the TC-net 100 network or in the TN8 module itself, the in-ring map is cleared to zero. The information in the in-ring map is updated in cycles of 10ms.
Use port numbers from 1024 to 65535 other than above. Version combination The following combination is required for TN821A/TN822A. Table 7-3 TN821A/TN822A Support Version Module Support Firmware version ○ V01.10 ~ TN821A/TN822A Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Chapter 7 Application Interface Restriction on Station Redundant Configuration If a station redundant configuration is used with the TN8 module, there are the following restrictions. Restrictions on the RAS information block If a station redundant configuration is used with the TN8 module, do not register any RAS information block because RAS information generated by the TN8 module cannot be used.
Appendix A Specifications A.1 General Specifications ··································· 72 A.2 TC-net 100 Transmission Specifications ··········· 73 A.3 Function Specifications ·································· 74 A.4 Serial Communication Port (RS-232C) Transmission Specifications ··············································· 75...
Appendix A Specifications A.1 General Specifications Table A-1 General specifications Specification Item TN821/TN821A/TN822/TN822A Operating temperature 0 to 55°C range (product ambient temperature) Operating humidity range 10 to 95%RH (no condensation) Storage temperature range -40 to 70°C Storage humidity range 5 to 95%RH (no condensation) Power voltage range 4.75 to 5.25VDC (Rating: 5.0VDC) Current consumption...
Change detection cycle Change detection words×30μs Detection signal interval 50ms or more Interface Optical MT-RJ type optical connector Cable Optical Quartz GI cable (62.5/125, long wavelength) or (50/125, long wavelength) Unified Controller nv series TC-net 100 (TN8) Module Operation Manual...
Page 93
Appendix B Outside Dimensions The following figure shows the outside dimensions of the TN8. TN822 SCAN MODE TOOL 約 262mm About 262mm 233.35mm LNK-A ACT-A TN-A LNK-B ACT-B TN-B Station bus connector About About 約 35mm 160.00mm 12mm About 20mm Figure B-1 TN8 (TN822/TN822A) outside dimensions 6F8C1360...
Page 95
Appendix C Related Products Table C-1 Related products Product name Rating Remark Optical fiber cord with MT-RJ Optical fiber cord optical connector at both Cable in board ends 9-pin RS-232C cable Standard length 5m D-sub 6F8C1360...
Page 96
Appendix D Decimal-hexadecimal Conversion Table...