6. PROFIdrive acyclic parameter access

In PNE001Z, inverter parameters and PROFIdrive parameters are accessible by acyclic communications
in addition to the cyclic communication via Telegram 100 or101.

6.1. Example1. Read the PROFIdrive parameter

6.1.1.
Request data table (Read PNU 964 (0x03C4) IND 0)
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Address (Byte 1)
Parameter Address (Byte 2)
Parameter Address (Byte 3)
Parameter Address (Byte 4)
Parameter Address (Byte 5)
Parameter Address (Byte 6)
6.1.2.
Response data table (positive)
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Value (Byte 1)
Parameter Value (Byte 2)
Parameter Value (Byte 3)
Parameter Value (Byte 4)
Field
Request Reference
Request ID (0x01: Request)
Axis
Number of Parameters
Attribute (0x10: Value)
Number of Elements
Parameter number (PNU), High byte
Parameter number (PNU), Low byte
Sub index (IND), High byte
Sub index (IND), Low byte
Field
Request Reference (mirrored)
Response ID
Axis (mirrored)
Number of Parameters
Format
Number of Values
Values, High byte
Values, Low byte
Description
Description
- 39 -
E6582051
Value
0x01
0x01
0x01
0x01
0x10
0x01
0x03
0xC4
0x00
0x00
Value
0x01
0x01
0x01
0x01
0x06
0x01
0x01
0x90