5.5.6.
fd01 (Inverter operating status 1 (real time))
bit
Function
0
Failure FL
1
Failure
2
Alarm
3
Under voltage (moff) Normal
Motor selection (1 or 2)
4
(THR 2 selection)
5
PID control off
Acceleration/deceleratio
6
n pattern selection (1 or
2)
7
DC braking
8
Jog run
9
Forward / reverse run
10
Run/stop
11
Coast stop (ST = OFF)
12
Emergency stop
13
Standby ST=ON
14
Standby
15
(Undefined)
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgment.
5.5.7.
fd00 (Output frequency (real time))
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- fd22 (Feedback value of PID (real time)) ............................. Unit: 0.01Hz
- fd16 (Estimated speed (real time)) ....................................... Unit: 0.01Hz
- fd29 (Input power (real time)) ............................................... Unit: 0.01kW
- fd30 (Output power (real time)) ............................................ Unit: 0.01kW
0
1
No output
Under in progress -
Not tripped
Tripped
No alarm
Alarm issued
Under voltage
Motor 1 (THR1)
Motor 2 (THR2)
PID control
PID control
permitted
prohibits
Acceleration/dec
Acceleration/dec
eleration pattern
eleration pattern
1 (AD1)
2 (AD2)
Forced DC
OFF
braking
OFF
Jog run
Forward run
Reverse run
Stop
Run
ST=ON
ST=OFF
No emergency
Emergency
stop status
stop status
Start-up process Standby
Start-up process Standby
-
-
- 31 -
E6582051
Note
Trip status includes rtry and
the trip retention status are also
regarded as tripped statuses.
-
-
THR1: pt = setting value, vl,
vlv, vb, thr
THR2: pt = 0, f170, f171,
f172, f173
-
AD1: acc, dec
AD2: f500, f501
-
-
-
-
-
-
Standby: Initialization
completed, not failure stop
status, not alarm stop status
(moff, ll forced stop),
ST=ON, and RUN=ON
Standby: Initialization completed,
not failure stop status and not
alarm stop status (moff, ll
forced stop)
-