Toshiba PNE001Z Function Manual page 33

Tosvert vf-s15 profinet option
Table of Contents

Advertisement

5.5.2.
fa23 (Communication command 2)
bit
Function
0
(Reserved)
Electric power quantity
1
reset
2
(Reserved)
3
(Reserved)
4
(Reserved)
5
(Reserved)
6
(Reserved)
Maximum deceleration
7
forced stop
Acceleration/decele-
8
ration selection 1
Acceleration/decele-
9
ration selection 2
10
(Reserved)
11
(Reserved)
12
OC stall level switch
13
(Reserved)
14
(Reserved)
15
(Reserved)
Note: Set 0 to reserved bit.
5.5.3.
fa07 (frequency reference from internal option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
5.5.4.
fa50 (Terminal output data from communication)
By setting up the data of the bit 0 - 1 of terminal output data (fa50) from communication, setting data
(OFF or ON) can be outputted to the output terminal.
Please select the functional number 92 - 95 as the selection (f130 - f138) of the output terminal
function before using it.
bit
Output TB function name
Specified data output
0
(Output terminal No.: 92, 93)
Specified data
1
(Output terminal No.: 94, 95)
2-15
(Reserved)
Note: Set 0 to reserved bit
5.5.5.
fa51 (Analog output (FM) data from communication)
Use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication data
output).
This makes it possible to send out the data specified as FM analog output data (fa51) though the FM
analog output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the VF-S15 instruction manual for details.
0
1
-
-
OFF
Reset
-
-
-
-
-
-
-
-
-
-
Normal
Enabled
00: Acceleration/deceleration 1
01: Acceleration/deceleration 2
10: Acceleration/deceleration 3
-
-
-
-
OC stall 1
OC stall 2
-
-
-
-
-
-
1
output 2
- 30 -
Note
-
Electric power quantity (fe76,
fe77) reset
-
-
-
-
-
-
Select acceleration/deceleration
1-4 by combination of two bits..
AD1: acc, dec
AD2: f500, f501
AD3: f510, f511
-
-
OC stall 1: f601
OC stall 2: f185
-
-
-
0
1
OFF
ON
OFF
ON
-
-
E6582051

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents