4.3. ZSW Status Word Data

Bit
Value
1
Ready To Switch-on
0
0
Not Ready To Switch-on
1
Ready To Operate
1
0
Not Ready To Operate
1
Operation Enabled
2
0
Operation Disabled
1
Fault Present
3
0
No Fault
1
Coast Stop Not Activated
4
0
Coast Stop Activated (OFF 2)
1
Quick Stop Not Activated
5
0
Quick Stop Activated (OFF 3)
1
Switching On Inhibited
6
0
Switching On Not Inhibited
1
Warning Present
7
0
No Warning
Speed Error
1
Within Tolerance Range
8
Speed Error
0
Out Of Tolerance Range
1
Control Requested
9
0
No Control Requested
1
f Or n Reached Or Exceeded
10
0
f Or n Not Reached
11
----
Device-specification
12
----
Device-specification
13
----
Device-specification
14
----
Device-specification
15
----
Device-specification
Name
Power supply is switched on
-
Refer to control word, bit 1.
-
Drive follows set point.
(Refer to control word 1, bit 3)
-
Inverter tripped.
Inverter is not tripped.
-
"Coast Stop (OFF 2)" command is present.
-
"Quick Stop (OFF 3)" command is present
Control word bit1 or 2 is set to 0
or fault trip has been acknowledged.
-
Drive still operational: Alarm in service parameter: No
acknowledgement.
Alarm not present or alarm has disappeared again
Refer to section 4.3.1.
Inverter is controlled by PROFINET master.
Inverter is controlled by another interface.
Actual value ≥ Comparison value (setpoint)
-
(Reserved.)
(Reserved.)
(Reserved.)
(Reserved.)
(Reserved.)
- 22 -
E6582051
Note