Parameters; Communication Parameters - Toshiba PNE001Z Function Manual

Tosvert vf-s15 profinet option
Table of Contents

Advertisement

3. Parameters

3.1. Communication parameters

This option doesn't operate if these parameters are not correctly set.
Communi
Title
cation No.
0003
Command mode selection
cmod
Frequency setting mode
0004
fmod
selection 1
Setting of acceleration /
0519
f519
deceleration time unit
Integrating wattmeter display
0749
f749
unit selection
Number of motor pole pair for
0856
f856
communication
0899
Communication function reset
f899
C081-
c081-
Device Name 1-16 (*2)
C096
c096
(*1): Default setting values vary depending on the capacity.
(*2): (typ) does not work for this parameter.
(*3): 0.1s unit is selected as default setting.
Function
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communcation option
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sr0
0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)
0:1=1kWh
1:1=10kWh
2:1=100kWh
3:1=1000kWh
4:1=10000kWh
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: -
1: Reset (after execution: 0)
16 characters
The device name is required if the card uses DHCP
to obtain its IP Address.
- 14 -
Description
E6582051
Default
setting
1
0
0
(*3)
(*1)
2
-
0