5.8. Access to drive parameter

When access to drive parameter, set "1" to the PNU. The communication number of the drive parameter is
set to the sub index IND.
Refer to the drive instruction manual about the communication number and unit.
* This procedure changes the value of drive EEPROM.
5.8.1.
Examples of reading or changing drive parameter
5.8.1.1. Example 1. Reading the basic parameter (
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0003 (
PKE
0
6
Requirement
PKW
PKE
60
Response (Value: 0x0001 = Operation panel))
40
5.8.1.2. Example 2. Reading the extended parameter (
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0219 (
PKE
0
6
Requirement
PKW
PKE
60
Response (Value: 0x1770 (= 6000 -> 60.00Hz *))
40
* "0x1770" as reading value of "VIC input point 2 frequency" is 0x1770 = 6000 (decimal number)
Since the unit of "VIC input point 2 frequency" is 0.01Hz, set the following value.
6000×0.01 = 60.00Hz
communication number)
cmod
1
1
0
0
0
0
IND
01
00
03
01
00
03
communication number)
f219
1
1
0
0
0
0
IND
01
02
19
01
02
19
- 37 -
(command mode selection))
cmod
0
0
0
0
0
PWE
00
00
00
00
00
00
00
01
(VIC input point 2 frequency))
f219
0
0
0
0
0
PWE
00
00
00
00
00
00
17
70
E6582051
0
0
0
0
0
1
PZD
・・・
・・・
・・・
・・・
0
0
0
0
0
1
PZD
・・・
・・・
・・・
・・・
1
1