5.7.3 To Individual Module Mounting Assembly(s) Equipped with Molex Connectors and
Provided with Rectifier AC Input Cable Assemblies or Rectifier AC Input Line Cords
Spec. No. 588705300 module mounting assembly(s) may be equipped with plug-in input connectors located on the rear of the
assembly. Input cable assemblies and line cords with mating connectors are available (see Power Data Sheet PD588705300). Refer
to Power Data Sheet PD588705300 for connection details.
Locate the module position identification label either on the inside of the distribution cabinet door (rack mounted systems) or inside
the OSP cabinet when no door is furnished. As the system is being wired for module inputs, write the type of module to be placed in
each module mounting position in the space provided on the label. Write R for rectifier, C for converter, and S for solar converter. See
Figure 5.6.
For systems using Molex connected cords and -48 VDC to +24 VDC converters or -48 VDC to -58 VDC converters are being used
(List 26 two row distribution panel or List 27 single row distribution panel) in the plant, the following module restrictions apply for
factory installed shelves 2 through 5:
Rectifiers can be in any or all six (6) positions if three (3) AC inputs provided.
+24V or -58V converters can be in the right three (3) positions (positions 4, 5 and 6).
Rectifiers can be in any position which has AC power that is not taken up with a converter.
One (1) Solar converter can be installed in the shelf, position 1 or 2.
Three (3) solar converters can be installed in the shelf, positions 1 or 2, positions 3 or 4 and positions 5 or 6 if the -48V to
+24V or -48V to -58V bus bar is not installed to the shelf above.
Proprietary and Confidential © 2023 Vertiv Group Corp.
Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
77