Precondition
Releasing the actuating
opening
Switching to EARTHED
position
Final activities
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
17.3
Switching the three-position switch-disconnector from OPEN to
EARTHED position
• Three-position switch-disconnector in OPEN position
➭ Check service readiness (see page 85, "Ready-for-service
indicator").
➭ Verify safe isolation from supply of the feeder (see page
104, "Verification of safe isolation from supply").
➭ Remove the padlock (optional) from the locking device.
➭ Push the control gate (optional) downwards, and hold it.
✔ The actuating opening of the earthing switch is open.
➭ Insert the operating lever and turn straight clockwise as
far as it will go.
✔ The position indicator of the earthing switch shows the
EARTHED position.
✔ The feeder is earthed.
➭ Remove the operating lever. The control gate returns to its
initial position.
➭ Fit the padlock (optional) on the locking device in the
desired position (see page 87, "Mechanical interlocking
with padlock").