Siemens 8DJH Installation And Operating Instructions Manual page 18

Medium-voltage switchgear
Table of Contents

Advertisement

Description
Cable type
Thermoplastic-insulated cables ≤ 12 kV according to IEC / EN 60502-2 / VDE 0276-620
1- or 3-core cable,
PE and XLPE-insulated
N2YSY (Cu) and N2XSY (Cu)
or
NA2YSY (Al) and NA2XSY (Al)"
Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC / EN 60502-2 / VDE 0276-620
1- or 3-core cable,
PE and XLPE-insulated
N2YSY (Cu) and N2XSY (Cu)
or
NA2YSY (Al) and NA2XSY (Al)
Paper-insulated mass-impregnated cables ≤ 12 kV according to IEC / EN 60055-2 / VDE 0276-621
3-core cable, paper-insulated
N(A)KLEY, N(A)KBA, N(A)KBY
3-core cable, paper-insulated
N(A)EKBA, N(A)KLEY
Paper-insulated mass-impregnated cables 15 / 17.5 / 24 kV according to IEC / EN 60055-2 / VDE 0276-621
1-core or 3-core cable, paper-
insulated
N(A)EKBA, N(A)KLEY
18/121
Cable plugs for single cable connection (interface type C)
Cable plug
Make
Nexans
nkt cables
Südkabel
Prysmian Kabel und Systeme
(Pirelli Elektrik)
3M Germany
TE Connectivity
Nexans
nkt cables
Südkabel
Prysmian Kabel und Systeme
(Pirelli Elektrik)
3M Germany
TE
for 1-core
Connectivity
cables
for 3-core
cables
TE Connectivity
TE Connectivity
1
T = Cable T-plug, W= Cable elbow plug
2
Use of current transformers and current sensors in combination with insulated systems on request
3
Discontinued by the manufacturer
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • 500-8067.9
Ser.
Type
no.
1
400TB/G, 430TB/G, 480TB/G T
2
400LB/G
3
484TB/G
4
440TB/G
5
CB 24-630
6
AB 24-630
7
CB 36-630 (1250)
8
SET 12
9
SEHDT 13
10
FMCTs-400
11
93-EE 705-6 / -95
12
93-EE 705-6 / -240
13
3
RICS 51 ... with IXSU
14
3
RICS 31 ... with IXSU
15
RSTI-39xx
16
K400TB/G, 430TB/G, 480TB/
G
17
K400LB/G
18
484TB/G
19
K440TB/G
20
CB 24-630
21
AB 24-630
22
CB 36-630 (1250)
23
SET 24
24
SEHDT 23.1
25
SEHDT 23
26
FMCTs-400
27
93-EE 705-6 / -95
28
93-EE 705-6 / -240
29
3
RICS 51 ... with IXSU
30
RSTI-58xx
31
RSTI-59xx
32
3
RICS 51 ... with IXSU
33
RSTI-58xx + RSTI-TRFxx
34
RICS 51... with UHGK / EPKT T
35
3
RICS 51... with IDST 51
36
RICS 51 ... with IDST 51
Design
Conductor
1, 2
T/W
cross-
section
2
[mm
]
35...300
W
35...300
T
70...630
T
185...630
T
25...300
T
25...300
T
300...630
T
50...300
T
185...500
T
25...300
T
50...95
T
95...240
T
25...300
T
25...300
T
400...800
T
35...300
W
35...300
T
70...630
T
185...630
T
25...300
T
25...300
T
300...630
T
50...240
T
300
T
185...630
T
25...240
T
25...95
T
95...240
T
25...300
T
25...300
T
400...800
T
25...300
T
25...300
95...300
T
50...300
3
T
35...240
2
Design
Screened
Screened
Screened
Screened
Screened
Insulated
Screened
Screened
Screened
Screened
Screened
Screened
Insulated
Insulated
Screened
Screened
Screened
Screened
Screened
Screened
Insulated
Screened
Screened
Screened
Screened
Screened
Screened
Screened
Insulated
Screened
Screened
Insulated
Screened
Insulated
Insulated
Insulated