➭ Insert the operating lever and turn counter-
clockwise as far as it will go.
✔ The position indicator of the disconnector
shows the OPEN position.
✔ The three-position disconnector is open.
➭ Remove the operating lever.
✔ The control gate returns to its initial
position.
➭ Fit the padlock (optional) on the locking
device in the desired position (see page 87,
"Mechanical interlocking with padlock").
19.6

Switching the three-position disconnector from OPEN to EARTHED position

• Circuit-breaker in OPEN position
• Three-position disconnector in OPEN position
➭ Check service readiness (see page 85,
"Ready-for-service indicator").
➭ Verify safe isolation from supply of the
feeder (see page 104, "Verification of safe
isolation from supply").
➭ Remove the padlock (optional) from the
locking device of the three-position
disconnector.
➭ Push the control gate of the three-position
disconnector downwards, and hold it.
✔ The actuating opening of the earthing
switch is open.
➭ Insert the operating lever and turn clockwise
as far as it will go.
✔ The position indicator of the earthing switch
shows the EARTHED position.
➭ Remove the operating lever.
✔ The control gate returns to its initial
position.
➭ Fit the padlock (optional) on the locking
device in the desired position (see page 87,
"Mechanical interlocking with padlock").