Standard accessories
(selection)
Other accessories
Features
Shipping data and
transport data
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
7.12

Accessories

• Operating and installation instructions
• Operating lever for disconnector, switch-disconnector and circuit-breaker (different
designs)
• Double-bit key with 3 mm diameter for low-voltage door (option)
According to the order documents / purchase order (selection):
• Surge arresters
• Surge limiters
• Cable plugs
• HV HRC fuse-links
• Test fuses for mechanical simulation of the striker of HV HRC fuse-links in transformer
feeders, with extension tube (for slide lengths 292 mm or 442 mm)
• HR or LRM voltage indicators
• Units to check the capacitive interface and the voltage indicators
• Unit to test the plug-in voltage indicators
• Phase comparison test units
7.13

Low-voltage compartment (option)

• Overall height: 200, 400, 600 or 900 mm
• Installation on the panel is possible per feeder
• Customer-specific equipping of the low-voltage compartment
• Option: Wiring duct for laying the panel-overlapping wiring on panels without low-voltage
compartment
• Option: Cover for switchgear fronts of the same height on panels without low-voltage
compartment
When switchgear assemblies are delivered with low-voltage compartments, the changed
transport dimensions and transport weights as well as the relocation of the center of gravity
must be observed.